Electrical Characteristics
Table 2-6.1: Outdoor unit electrical characteristics
Capacity
Model
Power Supply
1
Compressor
OFM
Hz
Volts
Min.
Max.
MCA
2
TOCA
3
MFA
4
MSC
5
RLA
6
kW
FLA
volts
volts
7HP
MVi-200WV2RN1(A)
50
380~415
342
456
19
24.3
25
/
12
2×0.17
2.1+2.1
8HP
MVi-224WV2RN1(A)
50
380~415
342
456
19
24.3
25
/
12.4
2×0.17
2.1+2.1
9HP
MVi-260WV2RN1(A)
50
380~415
342
456
20.5
24.3
25
/
15
2×0.17
2.1+2.1
10HP
MVi-280WV2RN1(A)
50
380~415
342
456
21
24.3
25
/
18.4
2×0.17
2.1+2.1
12HP
MVi-335WV2RN1(A)
50
380~415
342
456
26.4
33.2
32
/
19.6
2×0.17
2.1+2.1
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Full
Load Amps
Notes:
1.
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage
variation between phases is 2%.
2.
Select wire size based on the value of MCA.
3.
TOCA indicates the total overcurrent amps value of each OC set.
4.
MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5.
MSC indicates the maximum current on compressor start-up in amps.
6.
RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.