INSTALLATION CLEARANCES
Maintenance space
Left
side
Right
side
Strong and durable ceiling
Indoor unit
)
m
c
0
3
(
n
i
8
.
1
1
>
)
m
c
0
1
(
n
i
4
>
>0.8in(2cm)
>
0.8in(2cm)
>
11.8in(30cm)
(
ni
2.
8
>)
mc
0
5
2
Floor
Service access
Ceiling
)
g
nili
ec
o
n
n
e
h
W(
Ceiling opening size
Access Panel
Ceiling opening size
Fig. 6
-
Installation Clearances
MAINTENANCE CLEARANCES
>
11.8in
(
30cm
)
Service access
Service access
Unit
Width of the Unit
Coil Connection Area
Condensate Drain Piping Area
Condensate Pump Service Clearance
Sensor Service Clearance
B
Depth of unit
Access Panel
17.7 in (45cm) x 17.7 in (45cm)
7.8 in (20cm)
>11.81 in (30cm)
>4 in (10cm)
Bottom Return
Blower/Motor Service Clearance
Filter Service Clearance
Blower/Motor Service Clearance
PCB Board Service Clearance
Fig. 7
-
Maintenance Clearances
Table 5—Maintenance Clearances
Capacity (Kbtu)
B
9K
11.81in.(30cm)
12K
11.81in.(30cm)
18K
11.81in.(30cm)
24K
11.81in.(30cm)
36K
11.81in.(30cm)
48K
15.75in.(40cm)
58K
15.75in.(40cm)
NOTE: If installed above a hard lid ceiling, utilize a ceiling access panel the length and width of the unit, otherwise the blower components and/or
entire unit cannot be removed.
If a single access panel is desired, the minimum dimensions should be:
S
Width: The width of the unit plus 2−inches on both sides
S
Length: The length of the unit plus 18−inches on the connection end and 2−inches on the opposite end