Twin Split – Ducted / CF
5
•
Interconnecting power supply must be locally
isolated with a 5amp switch fuse spur to protect
the indoor PCB
•
Controller only wires to the Master
•
Link Fan coils on XY terminals with 2 core CY
•
The XYE adapter plug in is required to allow the
connection
•
Master and Slave are set using SW5
SW5 Bit 1 ON for Master
SW5 Bit 1&2 ON for the Slave