Midco International Inc.

8471 95

 

There are several parameters that can be adjusted for the speci

fi

 c application. The  

 

 

 

adjustable parameters are as follows.

 - 

APP

 

 

a.  Determine the functionality of the inputs by specifying which type of burner the control  

 

 

 

is being used on.

 

 

b.  vA-A is for VA series burners that use an intermittent pilot.

 

 

c.  vA-B is for VA series burners that use an interrupted pilot.

 

 

d.  noX is for Midco Low-NOx series burners.

 

tLo and thi

 

 

a.  Use these parameters to adjust the minimum and maximum temperature set point that  

 

 

 

a user can set while outside of programming mode. 

NOTE

: These parameters only    

 

 

 

have an e

 ect on the operation of the burner when the burner is operated by a  

 

   temperature 

control.

 

FLo and Fhi

 

 

a.  Use these parameters to adjust the minimum and maximum speed that the    

 

 

 

 

combustion blower can achieve (displayed as a percentage of the maximum capacity

 

 

 

of the blower).

 

 

b.  Adjusting FLo will change the speed of the combustion air blower during ignition and

 

 

 

when in run mode at 2.0V DC. This e

 ectively changes the minimum 

fi

 ring rate. The    

 

 

 

default setting is 10% of maximum fan speed.

 

 

c.  Adjusting Fhi will change the speed of the combustion air blower while in run mode

 

 

 

with a 10.0V DC input signal. This e

 ectively changes the maximum 

fi

 ring rate of the    

 

 

 

burner. The default setting is 100% of maximum fan speed.

 - 

inPt

 

 

a.  This parameter is used to specify which type of input is used to control the modulation  

 

 

 

of the burner.

 

 

b.  dC is for using a 2-10V DC input signal sent from an external temperature controller.

 

 

c.  rE is used when one connects a discharge temperature sensor as well as an external

 

 

 

thermostat. The SCEBM-2 still modulates the burner based on the discharge

 

 

 

temperature and the temperature set point, but in this mode the temperature set point  

 

 

 

is set from an external device.

 

 

d.  tS is the setting used when one connects a discharge temperature sensor directly  

 

 

 

 

to the SCEBM-2 module. The SCEBM-2 then modulates the burner based on the  

 

 

 

 

discharge temperature and the temperature set point.

 - 

ovEr

 

 

a.  Enables or disables the manual override function. When enabled, the user can adjust   

 

 

 

the combustion fan speed manually using the up and down arrows. The input signal

 

 

 

from the external temperature controller or the discharge temperature sensor will be    

   overridden.
 - 

Pid

 

 

a.  This parameter is used to adjust how aggressively the SCEBM-2 module tracks

 

 

 

the discharge temperature. 

NOTE

: This parameter only has an e

 ect on the operation  

 

 

 

of the burner when the burner is operated by a temperature control.

 - 

oFS

 

 

a.  This parameter is used to adjust the discharge air sensor. 

NOTE

: This

 

 

 

parameter only has an e

 ect on the operation of the burner when the burner is  

 

 

 

 

operated by a temperature control.

 - 

ForC

 

 

a.  This parameter is used to choose whether the SCEBM-2 module displays the

 

 

 

temperature in degrees Fahrenheit or degrees Celsius. 

NOTE

: This parameter only    

 

 

 

has an e

 ect if there is a temperature discharge sensor hooked up to the SCEBM-2.

 - 

PASS

 

 

a.  This parameter enables or disables the password. If the password is enabled, one  

 

 

 

 

must enter it in order to access the program menu.

 - 

vEr

 

 

a.  The installed version of the software.

 

 

  

 

    __________________________________________

XIII         SCEBM-2 

Module

120V Burners 

Continued

B          Setting the

Parameters 

Part 2 Service - SCEBM-2 Module 120V Burners

Содержание Unipower V1

Страница 1: ...ctory for item availability Quality Designed for Proven Performance WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage pers...

Страница 2: ...5 1 19 1 26 1 Inlet Gas 4 NG pressure for maximum firing rate W C 10 0 10 0 10 0 10 0 10 0 10 0 10 0 10 0 10 0 10 0 10 0 10 0 Manifold gas NG pressure for maximum firing rate W C 5 0 3 4 3 9 3 9 4 3 4...

Страница 3: ...fasten the burner to the equipment either create four tapped holes on the front plate and use bolts to fasten the burner or install four threaded studs and fasten the burner with a washer and nut The...

Страница 4: ...main gas valve train to the union on the burner Figure 3 1 2 Connect the gas supply line to the shut o valve next to the main regulator Figure 3 2 3 Connect air pressure line from the compression fitt...

Страница 5: ...O Valve be installed outside Run full size pipe or tubing from regulator vent openings to outside of building Provide no traps in the vent lines and terminate away from all doors and windows also make...

Страница 6: ...to Figures 4A and 4B for Siemens control 120V On O switch 8 Neutral and 1 Ground refer to Figures 4C and 4D 24V Burner Models L1 Black L2 White and G Green refer to Figures 4E Note For 240 V versions...

Страница 7: ...M 4 BLOWER 10 F G BL BL W BL BR BR W BR W BR BK G O W BL W 14 15 BLOWER 16 Y R BL BL W BL G G 13 SCEBM 2 FAN W 15 6 B Y A 14 13 SCEBM 2 2 10V COM BL Y 24V RED ORN 120V SCEBM 2 24VAC 8 7 BK 6 8 4 9 BK...

Страница 8: ...2 2 BL O O W W 14 13 9 5 4 5 6 7 8 9 10 11 12 TERMINAL STRIP JUMPERS LEGEND F 5 SOLID WIRING AND DASHED WIRING AND ENCIRCLED FLAME SOLID ROUND OPEN ROUND COMPONENT 12 14 13 9 5 8 4 1 RELAY SOCKET COMP...

Страница 9: ...03 1 2 3 4 2 X2 01 3 1 4 3 2 1 X2 02 X6 03 1 3 2 X3 04 1 3 2 4 5 X2 03 2 3 1 X10 06 1 2 3 X10 05 2 1 4 5 X4 02 2 3 1 4 3 2 1 X7 04 X7 01 1 3 2 PME71 111A1 DISPLAY OFF Standby waiting for call for heat...

Страница 10: ...2 3 X10 05 2 1 4 5 X4 02 2 3 1 4 3 2 1 X7 04 X7 01 1 3 2 PME71 111A1 DISPLAY OFF Standby waiting for call for heat P24 Fan motor on Actuator opens in high fire P30 Prepurging P36 Actuator closes to ig...

Страница 11: ...OWER BK SCEBM 1 P3 P1 W P9 SCEBM 1 P11 SCEBM 1 BLOWER BLOWER P13 SCEBM 1 BLOWER Y R BL Y R BL 12 P2 SCEBM 1 TEMPERATURE CONTROL P4 SCEBM 1 O W O 2 1 9 7 8 10 SPARK SENSE W BK SE SP BR BR BR BL BL BL B...

Страница 12: ...the burner run and is not reestablished within 15 seconds after the prepurge the ignition system will shut o the Automatic Safety Shut o Valves and LOCK OUT For the 120V models RESET the flame safegu...

Страница 13: ...3 Turn the burner up to its actual firing rate applying an input signal of 10V DC for maximum firing rate 4 Confirm that the inlet pressure remains between the maximum and minimum values specified on...

Страница 14: ...o regulator See Figure 9 item 3 page 20 for location 2 Use flexible tubing to hook up a manometer to the barb fitting 3 Turn the burner on and adjust the temperature controller to its maximum setting...

Страница 15: ...to high fire by applying a 10V DC input signal Verify that the manifold pressure is the same as marked on the Burner Rating Label s for the actual firing rate ________________________________________...

Страница 16: ...5 Fill out the installation adjustment data tag and a x to the burner or gas utilization equipment NOTE For subsequent normal starting and shut o procedure refer to CONSUMER INSTRUCTIONS located in Se...

Страница 17: ...put gas pressure The motor used in this burner is variable speed By using this air pressure relation in the blower output gas pressure can be varied relative to the air pressure through a ratio regula...

Страница 18: ...l for heat Burner is Energized Pre purging sequence initialized Relay A is energized SCEBM 2 Control will read PRGE Blower accelerates to high speed Low pressure air switch is closed Pre purging Blowe...

Страница 19: ...on Flame safeguard initializes pilot flame for 10 seconds trial for ignition Pilot valve opened and spark initialized SCEBM 2 Control will read PIL Blower decelerates to lowest speed Did the pilot fla...

Страница 20: ...alized and begins 30 second pre purge Pilot initialization Honeywell S8760J initializes pilot flame for 15 second trial for ignition Pilot valve opened and spark initialized SCEBM 1 Control will shine...

Страница 21: ...termittent O O PRGE Open 100 Pilot On O PIL Closed Min On On RUN Open Modulate O On ERR Open Min Interrupted O O PRGE Open 100 Pilot On O PIL Open Min On On IGN Open Min O On RUN Open Modulate PRGE Pu...

Страница 22: ...n with the up and down arrows then pressing enter to save the selected setpoint Column 1 shows the menu parameters Arrow Keys Up and Down to navigate or adjust a menu parameter Right to access column...

Страница 23: ...when one connects a discharge temperature sensor as well as an external thermostat The SCEBM 2 still modulates the burner based on the discharge temperature and the temperature set point but in this...

Страница 24: ...ntrol signal B MOTOR RUNS CONTINUOUSLY PILOT WILL NOT LIGHT 1 Confirm that ALL Main Manual Shut O Valves are Open 2 After pre purge if the pilot flame is not proven within the pilot flame re establish...

Страница 25: ...l valve 1 leak Loc 13 Loc 13 Valve proving Fuel valve 2 leak Loc 14 Loc 14 POC error Error valve closure control POC Loc 22 Loc 22 Safety loop open Gas pressure switch max open Safety limit thermostat...

Страница 26: ...nc 8471 95 XVI Trouble Shooting for 120V Burners Continued E Siemens Control Sequence of Operation for 120V Burners Chart 9 Siemens Control Sequence of Operation 120V Burners Part 2 Service Trouble Sh...

Страница 27: ...meaning of the error and diagnostic codes see Error code list in Chart 8 Chart 10 Siemens Control Display of Flame Current 120V Burners F Siemens Control Display of Flame Current for 120V Burners XVI...

Страница 28: ...uring the burner run and the pilot is not re established after the pre purge the Ignition Control Module will lock out RESET the 24 volt ignition Control Module by setting the operating control to OFF...

Страница 29: ...to V10 2 2101 01 Burner Housing V2 3 N A Main Gas Manifold Pressure Tap 4 N A Manual Firing Valve 5 N A Air Pressure Tap 6 8416 14 Low Fire By Pass 7 8416 04 Dungs FRG Ratio Regulator Item Part Descri...

Страница 30: ...p 6 8416 14 Low Fire By Pass 7 8416 04 Dungs FRG Ratio Regulator 8 8402 42 Main Gas Solenoid Valve 1 9 8402 42 Main Gas Solenoid Valve 2 10 8416 05 Main Gas Regulator 11 8404 67 Main Manual Gas Shut o...

Страница 31: ...ld Casting 2 8699 30 Air Pressure Tubing to Dungs FRG 3 8699 30 Air Pressure Pickup Tube 4 8433 24 Spark Rod 5 2112 01 Pilot 6 8433 25 Flame Rod 7 8699 30 Pilot Gas Line 8 8699 30 Air Pressure Tubing...

Страница 32: ...using Rear 24V Burners 1 N A Aluminum Manifold Burner Casting 2 8699 30 Air Pressure Tubing to Dungs FRG 3 8699 30 Air Pressure Pickup Tube 4 8433 24 Spark Rod 5 2112 01 Pilot 6 8433 25 Flame Rod 7 86...

Страница 33: ...ot 2 8433 25 Flame Rod 3 8433 24 Spark Rod 4 N A Burner Gas Manifold 5 N A Gas Orifices 6 2122 10 High Temperature Flange Gasket 7 2113 50 Side Plate 8 N A Main Gas Manifold Pressure Tap 9 2110 00 Ba...

Страница 34: ...65 9 33 15 35 1 2112 01 Pilot 2 8433 25 Flame Rod 3 8433 24 Spark Rod 4 N A Main Gas Manifold Pressure Tap 5 2113 50 Side Plate 6 2110 00 Ba e 7 2122 10 High Temperature Flange Gasket Item Part Descr...

Страница 35: ...ens Control Box 120V Burner 1 8429 78 SCEBM 2 Fan Control 2 8447 28 120 208 24vac 24V 40VA Transformer 3 8402 50 Pilot Solenoid Valve 4 8409 25 Terminal Block 5 8406 98 99 Relay B 6 8406 95 96 Relay A...

Страница 36: ...06 Control Box Shelf 4 8429 57 Ignition Control 5 8429 02 SCEBM 1 6 8447 34 100VA Main 24VAC Transformer 7 8406 58 24VAC Relay 8 8408 78 120VAC Terminal Strip 9 8406 83 Nine Second Relay Timer 10 840...

Страница 37: ...shed within 10 seconds after the pre purge the controller will shut o the automatic safety shut o valves and lockout 6 Reset the flame safeguard 7 Repeat step 4 for restart To shut o 1 Close manual ga...

Страница 38: ...ag b Protected from shipping damage c Received transportation pre paid at Midco International Inc Return Goods Dept 4140 West Victoria Street Chicago Illinois 60646 6727 d Found by Midco s inspection...

Страница 39: ...returned scrapped repaired or replaced as instructed by the customer Products returned to the customer will be sent shipping charges collect Call factory for information 866 705 0514 Fill out form an...

Страница 40: ...95 ISO 9001 C O MPAN Y R E G ISTER E D Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 toll free 866 705 0514 tel 773 604 8700 fax 866 580 8700 web www midcointernational com...

Отзывы: