14
Midco International Inc.
8471 95
6. Use a manometer to check the manifold pressure near where the valve train attaches to
the burner, see Figure 10 - item # 3 page 30.
7. Use another manometer to check the load pressure on the ratio regulator, see
Figure 10 - item # 5 page 30.
8. Modulate the burner until the load line pressure is 2.0
″
W.C. by adjusting the input
voltage to the burner.
9. Verify that the manifold pressure is within the values given in Chart 2 page 15.
10. If necessary turn the screw on the ratio regulator, see Figure 6A & 6B below, in order to
adjust the manifold pressure.
24V Burners
Model
Pressure
V1-
V2
0.8-0.9
″
W.C.
__________________________________________
1. With the burner o
ff
, install a barb
fi
tting on the
⅛″
NPT pressure tap downstream of the ratio
regulator. See Figure 9 item #3 (page 20) for location.
2. Use
fl
exible tubing to hook-up a manometer to the barb
fi
tting.
3. Turn the burner on and adjust the temperature controller to its maximum setting. Measure the
manifold pressure and compare it to Chart 1 for 120V burners and Chart 2 & 3 for 24V burners.
For 120V Burner Models
4. Adjust the high
fi
re by turning the span knob on the
120V burner SCEBM-2 board.
Measure
the manifold pressure and refer to the
Chart 1 for the 120V
burner to match the manifold pressure
to the desired
fi
ring rate.
VI Initial
Start-up/Adjustment
for 120V and 24V
Continued
D V
erify the Ratio
Regulator
Adjustment
Continued
Table 3B. - Pressure Load Settings
E -
High Fire
Adjustment
i - Adjustment 120V
V1
V2
5
4
1.5
1
2.5
2
3.5
3
4.5
0.5
0
0
3500
3000
2500
2000
1500
1000
500
Manifold
Pressure
(Inches W.C.)
Firing Rate (mbtu/hr)
4000
V9 - V10
V7 - V8
V5 - V6
V3 - V4
Chart 1 -
Manifold Pressure vs. Firing Rate - VA 120V Burners
Part 1 Installation