4.3
Needed components for connection to water circuit
It is advised to use hose nut with external thread PN16 50 x 6/4” and a pressure hose D50 or PVC
pipe D50.
Particular component selection depends on individual condition at your pool. Your seller,
distributor or pool builder may decide on how the actual connection is performed. These
components are not part of heat pump package or delivery.
Sample connection scheme and application example
Important:
For proper operations, there must be a water flow through the heat pump
exchanger in range of
4-6 m
3
/hour
. In the case of water flow exceeding 10m
3
/h the
heat pump will turn itself off and an error notice EE5 will pop up. Repeated error
notice or repeated exposure of the heat pump to the water flow higher than 8m
3
/h
will cause irreversible damage to flow switch with permanent error notice EE5. The
heat pump will be turned off. Please contact your distributor or service department,
the flow switch needs to be replaced.
Picture: Pressure hose
D50
Error code ‚EE5‘ advising of low / high water
flow or damaged flow switch.
Picture: Hose nut with external thread PN16.
G=6/4” D=50mm
Picture: PVC pipe, various
dimesions
Picture: Sample water connection to the heat pump. Flexible hose glued
onto hose nut adapter with external thred that is tightened into the heat
pump exchanger thread.