Quick Start Guide 

Commissioning the 
Smart I/O Controller Digital 

 

V1.0.0 

 

 

 

 

Содержание MS660411M

Страница 1: ...Quick Start Guide Commissioning the Smart I O Controller Digital V1 0 0...

Страница 2: ...al with MICROSENS Switches 8 6 1 Defining and Assigning a Function Template 8 6 2 Pairing the Smart I O Controller Digital and the MICROSENS Switch 10 6 3 Functional Test of the Paired Smart I O Contr...

Страница 3: ...or mounting the device onto a standard top hat rail Figure 1 Pos 2 Note Assemble the clamp to the housing if not shipped with clamp already adapted Be sure the clamp s release lever Figure 1 Pos 3 is...

Страница 4: ...ach the Smart I O Controller Digital directly to a wall ceiling or any other suitable backing equipment use the four mounting brackets Figure 3 Pos 1 to 4 Figure 3 Mounting tabs Note Make sure to secu...

Страница 5: ...wer Out Power output 1x 24 VDC two wire cable Figure 4 Pos 3 maximum load 20 W Ethernet Ethernet uplink port 1x 10 100Base T RJ 45 PoE PD 54 VDC Figure 4 Pos 1 maximum internal consumption 25 W Note M...

Страница 6: ...potential and thus to avoid floating ground problems Besides safety issues a floating ground of the network can cause problems if only one component accidentally or on purpose is grounded Figure 5 Fig...

Страница 7: ...X1 X3 X5 X7 X9 X11 X13 X15 X17 X19 Digital In 1 Digital In 10 Digital input 10x max 24 VDC opto isolated the use of 24 VDC is recommended The port assignments are as follows X1 X19 Port voltage betwe...

Страница 8: ...orporate network the controller is accessible via a MICROSENS switch containing the MICROSENS SmartDirector Note Although it is possible to operate a remote Smart I O Controller Digital with a MICROSE...

Страница 9: ...ode Enables or disables each digital input port by checking or unchecking the respective option Note Enable the specific port to create the respective actor sensor status Din x attribute Defines the f...

Страница 10: ...to assign a specific instance number to the attribute by adding the number with a to the attribute name e g if a blind relay is connected to the digital output port Dout 1 but for whatever reasons sho...

Страница 11: ...lable Controllers As long as no device of the suitable product type is created previously the column Pairing Actions of the respective Smart I O Controller Digital is empty A click on the button ident...

Страница 12: ...g as no controller is found the section scanned Light Controllers stays empty After successfully scanning for available Smart Controllers the Web Manager lists all found controllers Figure 14 Web Mana...

Страница 13: ...t I O Controller Digital via the Web Manager of the paired MICORSENS switch Note For this overview primarily the use of the Web Manager is shown Using the CLI for pairing the devices is relatively eas...

Страница 14: ...roller named by its assigned attribute This corresponds to the attribute assignments Din x attribute defined in the controller s template configuration step see above The column instance incrementally...

Страница 15: ...wn firmware that can be manually updated via the Web Manager of a connected MICROSENS G6 switch To update the firmware prpceed as follows Using the Web Manager Start the web browser and enter the IP a...

Страница 16: ...o the tab Device Configuration Figure 20 Web Manager SmartOffice Device Configuration Update Firmware In the section Device smartoffice device_config scroll down to the respective controller In the fi...

Страница 17: ...er publisher and subscriber on the OSI transport layer The Smart I O Controller Digital communicates only via TCP port 1883 not Web socket 8083 The encryption for securely using credentials uses AES25...

Страница 18: ...t to configure within the following steps 5 For configuring MQTT change to the tab MQTT Figure 22 Smart Config Tool MQTT Parameters The parameters have the following meaning Connection Status Shows th...

Страница 19: ...ast will topic read write o Settings correspond to the MQTT mode settings above It is recommended to use a higher QoS level for last will topics Will Retain If set the broker saves the last will messa...

Страница 20: ...is device Device ip v4_status dynamic_device_ip e g 10 100 89 187 IP6 IPv6 address of this device if enabled Device ip v6_status ip e g fe80 260 a7ff fe09 374e 64 DMN Domain name of the Smart Office n...

Страница 21: ...ness completeness or quality of the information provided fitness for a particular purpose or consecutive damage Any product names mentioned herein may be trademarks and or registered trademarks of the...