Current Mode (Register 0x204)
Register Address: 0x204
The scalable current output provides filtered RPM or POSITION analog output depending
upon the chosen mode.
SPEED
Modes
Description
0
Bipolar output over 4mA to 12mA to 20mA where 12mA is equal to 0
RPM.
CW rotation from 0RPM to (Current Scale) RPM corresponds to 12mA to
20mA. Overrange extends from 20mA to 23mA (maximum)
CCW rotation from 0RPM to (Current Scale) RPM corresponds to 12mA to
4mA. Overrange extends from 4mA to 0mA (minimum).
1
Unipolar output range of 0-24mA where 0mA represents 0RPM,
regardless of direction.
2
Unipolar output range of 4-20mA where 4mA represents 0RPM,
regardless of direction.