2.2 - Algorithm of the time current curves
The Time Current Curves are generally calculated with the following equation :
(1)
where :
t(I) = Actual trip time delay when the input current equals I
Is = Set minimum pick-up level
K
=
T
s
= Set time delay : t(I) = T
s
when
tr
= Operation time of the output relay on pick-up.
The parameters A, B and a have different values for the different Time Current Curves.
Curve Name
Curve Identifier
A
B
a
IEC A Inverse
A
0.14
0
0.02
IEC B Very Inverse
B
13.5
0
1
IEC C Extremely Inverse
C
80
0
2
IEEE Moderate Inverse
MI
0.0104
0.0226
0.02
IEEE Short Inverse
SI
0.00342
0.00262
0.02
IEEE Very Inverse
VI
3.88
0.0963
2
IEEE Inverse
I
5.95
0.18
2
IEEE Extremely Inverse
EI
5.67
0.0352
2
For the IEC curves, being B = 0, the Time/Current equation (1), becomes:
Where Kt = (10
a
-1)Ts is the time multiplier