IM30-B00
Doc. N°
MO-0132-ING
Copyright 2010 - Microener
Firmware
2.0X
Data
22.04.2008
Rev.
2
Pag
10
of
23
7. Digital Inputs
Three digital inputs are provided: they are active when the relevant terminals are shorted
B2
(terminals 1 - 2)
:
it blocks the operation of the time delayed elements t1I and t2I.
B3
(terminals 1 - 3)
:
it blocks the operation of the time delayed elements t3I.
B4
(terminals 1 - 14)
:
Switching-over from Setting Program 1 (SP1) to Setting Program 2 (SP2)
- Terminals 1
– 14 Open = Setting Program 1 active
- Terminals 1
– 14 Shorted = Setting Program 2 active
The input B4 can also be activated via the serial communication port.
In this case Switching-back from SP2 to SP1 can only be made via serial
port.
Viceversa if the terminals 1
– 14 are shorted, switching-back from SP2 to
SP1 cannot be made via the serial port.
When a function is blocked the pick-up of its time delayed output is inhibited. Programming allows to
have the inhibition either permanent as long as the blocking input is active (tB2=Dis; tB3=Dis) or
automatically removed after the expiry of the set trip time delay of the function involved plus an
additional time 2tBF (tB2=2tBF; tB3=2tBF). By proper interconnection of the blocking inputs and outputs
of different relays it is possible to configurate very efficient arrangements of logic fault discrimination as
well as to feature a safe and quick breaker back-up protection.
8. Test
Besides the normal "WATCHDOG" and "POWERFAIL" functions, a comprehensive program of self-test
and self-diagnostic provides:
Diagnostic and functional test, with checking of program routines and memory's content, run every
time the aux. power is switched-on: the display shows the type of relay and its version number.
Dynamic functional test run during normal operation every 15 min. (relay's operation is suspended
for less than
4ms). If any internal fault is detected, the display shows a fault message, the Led
"PROG/IRF" illuminates and the relay R5 is deenergized.
Complete test activated by the keyboard or via the communication bus either with or without tripping
of the output relays.