![Microchip Technology GridTime 3000 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/microchip-technology/gridtime-3000/gridtime-3000_installation-manual_1786100019.webp)
...........continued
Name
Display
Clock
Information
Tab
CLOCK INFO
USB-C IP 0.0.0.0
Firmware:
Admin IP 192.168.2.100
1.0b1.01
S/N CC000112
Shows the serial number, the firmware version and the IP address of the administration port.
Clock Power
Tab
CLOCK POWER
Reboot
Shutdown
Accessed by holding the middle front panel button when on any other tab. Press the left button to
restart the device, the right button to shut down, or the middle button to return to the main tab.
Note:
The shutdown is a software shutdown only, and will not switch off power to the device or its
internal components.
3.2
Back Panel
This section describes the functionality on the GridTime
™
3000 GNSS Time Server’s back panel.
Figure 3-2. GridTime 3000 Back Panel Features
1.
RJ-48C T1/E1/J1 ports (x2)
2.
BNC Ports 1-2 -Fixed frequency/TTL ports (x2)
3.
BNC ports 3-6 -AM IRIG/TTL ports (x4)
4.
BNC ports 7-8 -IRIG in/TTL out ports (x2)
5.
RJ-12 RS232 and RS422 serial string output ports (x1 of each)
6.
ST optical fiber output port (x2)
7.
HV MOSFET port — (x1)
8.
Form-C Alarm Relay Ports — (x2)
9.
TNC GNSS antenna port (x1)
10. Earth Stud
11. Power supply port(s) (up to x2)
Physical Overview
©
2022 Microchip Technology Inc.
and its subsidiaries
Manual
DS00004572A-page 19