9.5.7.5.3 61850-9-3 Power Utility Profile Client Only Mode
This section describes how to provision a PTP 61850-9-3 Power Utility Profile Client Only Mode Clock.
1.
Select Client Only for PTP Clock Mode
Select 'Client Only' from the 'PTP CLOCK MODE' dropdown.
2.
Network Protocol
By default, the 'NETWORK PROTOCOL' is set to Layer 2 (Ethernet), which will send packets via the Ethernet
data layer
3.
Select Operating Mode
Select the operating mode for the PTP network from the 'OPERATING MODE' dropdown.
Operating mode is a network wide parameter. The configurable options are 'One Step' or 'Two Step'.
Note:
Select Two Step operation if the Operating Mode is unknown.
4.
Delay Mechanism
By default the 'DELAY MECHANISM' will be set to P2P, which will set the delay mechanism to peer to peer as
defined in IEEE 1588v2-2008.
5.
Configure Default Domain
Modify the 'DEFAULT DOMAIN' number if required, otherwise it is recommended that it is left as its default
value of '0'.
A domain consists of one or more PTP devices communicating with each other. By default, PTP aware
devices are configured with a domain of '0'. Changing the domain will cause only devices with the specified
domain to communicate using the PTP protocol. The input range is 0 to 127 and 254.
6.
Configure Delay Asymmetry
Modify the 'PRIMARY ETH PORT DELAY ASYMMETRY' setting if the delay asymmetry in the network link is
known, otherwise it is recommended that the setting is left as its default value of '0'.