Set Sensor Parameter
optoNCDT 1220
7.3
Inputs
7.3.1
Overview Functions
Go to the
Settings
menu.
Multifunctional
input
Zeroing
High / Low Sets the function of the switching input. The Trigger
influences export of a measurement value. Zeroing set
the current measurement value to half of the analog
output values. Teaching scales the analog output. HTL
is defined as active input level.
Trigger In
High / Low
Teaching
Inactive
Key function
Zeroing
Sets the function of the sensor key. Inactive means
keylock.
Teaching
Inactive
7.3.2
Zeroing
The zero setting function set the output value to half of the analog output values or to zero (digital value in
the web interface). The output range is moved thereby. This function makes sense, for example, for several
adjacent measuring sensors or in the case of the thickness and planarity measurement.
Zero setting is used to compensate mechanical tolerances in the measurement setup of the sensors or for
relative measurements. When zeroing the sensor‘s characteristic is parallel displaced.
Sequence for Zeroing:
Bring target and sensor in the desired position together.
Trigger the zero setting function via the hardware input or the button on the sensor.
After zero setting, the sensor will provide new readings relative to the measurement value during zero setting.
i
Zeroing
requires that a target is within the measurement range.
Zeroing
has an influence on the analog and digital output.