SD-100 Series Photoelectric Smoke Detectors 

Installation and Maintenance Instructions 

General Description 

Model SD-100-2WT: 2-Wire Photoelectric Smoke

Detector with Heat Sensor and Remote Indicator

Model SD-100-4WT: 4-Wire Photoelectric Smoke

Detector with Heat Sensor

All models incorporate a microprocessor with an 

advanced optical sensing chamber and feature a 

restorable, fixed temperature (135°F/57.2°C) thermal 

detector. SD-100 Series detectors are designed to 

provide open area protection.   

TYPICAL WIRING DIAGRAMS 

Figure 1(a) 

T

ypical wiring diagram of the 2-wire 

multiple-station smoke detector system.

   

Figure 1(b)

 Typical wiring diagram of the 4-wire 

multiple-station smoke detector system. 

CAUTION: DO NOT USE LOOPED WIRE UNDER TERMINALS 

2 AND 5. BREAK WIRE RUN TO PROVIDE SUPERVISION OF 

CONNECTIONS. 

MISE EN GARDE: POUR LE CONTRÔLE DES SYSTÈMES – 

POUR LES BORNES 2 ET 5, NE PAS UTILISER DE FIL 

ENROULÉ SOUS LES BORNES. COUPER LE CÂBLAGE POUR 

ASSURER LA SURVEILLANCE DES RACCORDEMENTS. 

WARNING 

TO PREVENT DETECTOR CONTAMINATION AND SUBSEQUENT 

WARRANTY  CANCELLATION,  THE  SMOKE  DETECTOR  MUST 

REMAIN COVERED UNTIL AREA IS CLEAN AND DUST FREE. 

AVERTISSEMENT 

POUR  ÉVITER  LA  CONTAMINATION  DU  DÉTECTEUR  ET 

ANNULER  LA  GARANTIE,  LE  DÉTECTEUR  DE  FUMÉE  DOIT 

RESTER  COUVERT  TANDIS  QUE  L'ENDROIT  EST  PROPRE  ET 

SANS CONTAMINER DES POUSSIÈRE. 

INSTALLING THE BASE 

Figure 2

 Installing 6” base 

Notes:

 The end-of-line devices shown in Figures 1(a) and 

1(b) must be compatible with the control panel. The 

end-of-line supervisory relay must be rated for the DC 

power voltage used. 

Open area smoke detectors are intended for mounting on 

a ceiling or a wall in accordance with the fire standard in 

your country. 

There is a limit of 21 smoke detectors on one loop. 

1. Ensure that all wires are properly identified, and fasten

the wires away from the connector terminals.

2. If you used a jumper wire to connect the poles of

terminals 2 and 5 when testing the detector loop

continuity, remove the jumper wire before you install

the detector head.

3. Mount the base of the smoke detector directly onto an

electrical junction box such as an octagonal (3”, 3.5” or

4”), a round (3”), or a square (4”) box without using

any type of mechanical adapter.

INSTALLING THE HEAD 

1. Thoroughly clean the area of construction debris and

dust.

2. Align the mark on the detector head with the short

mark on the base and twist the head clockwise to

secure it. The mark on the head should line up with the

long mark on the base.

Figure 3

 Attaching detector head onto base 

PUSH TAB WITH 

RAISED PLASTIC 

DOT AND TURN 

HEAD TO UNLOCK

RECTANGULAR
OPENING HERE

LED

DETECTOR HEAD

4” BASE

SHORT ALIGNMENT MARK

LONG ALIGNMENT MARK

RECTANGULAR
OPENING HERE

DETECTOR HEAD

LED

LONG ALIGNMENT MARK

SHORT ALIGNMENT MARK

6” BASE

INITIATING

LOOP

UL864

LISTED

COMPATIBLE

CONTROL

PANEL

+

-

FIRST DETECTOR BASE

LAST DETECTOR BASE

EOL

DEVICE

-

+

-

REMOTE 

INDICATOR

CLASS A OPTIONAL WIRING

NOTE: IF REMOTE INDICATOR IS NOT USED, REVERSING POLARITY ON DETECTOR IS 

PERMITTED.

+

2A

2B

6

5

4

3

1

2A

2B

6

5

4

3

1

INITIATING

LOOP

UL864

LISTED

COMPATIBLE

CONTROL

PANEL

+

-

FIRST DETECTOR BASE

LAST DETECTOR BASE

CLASS A OPTIONAL WIRING

+

POWER 

TO 

DETECTOR

-

2A

2B

6

5

4

3

1

2A

2B

6

5

4

3

1