background image

 

LT

6135

 

rev

 

1.1

  

7/16/19

         

25 Interchange way, Vaughan Ontario. L4K 5W3

Phone: 905.660.4655; Fax: 905.660.4113

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Web:  www.mircom.com

MIX-4001 / 4002 DETECTOR BASE                                                           

ABOUT THIS MANUAL

This manual is included as a quick reference for installation.  For fur-
ther information on the use of this device with a FACP, please refer to 
the panel’s manual.

Note:  This manual should be left with the owner/operator of this 
equipment

DETECTOR BASE DESCRIPTION

The MIX-4001and MIX-4002 bases are used to interface series 4000 
detectors to the SLC line and remote devices. The base can be wired 
and secured to a back-box during building construction, allowing the 
detector to be installed later, when premises become free of dust and 
other contaminants. The MIX-4001 and MIX-4002 both have a set of 
mounting holes covered by the detector head. These are used to 
mount the base to single gang boxes, 3.5" square boxes, and 4" 
octagonal boxes. The MIX-4001 has an extra set of outer holes, 
covered by a removable ring, for 4" square boxes (see figure 2). 
When the base is secured to the box, the ring is placed back to cover 
the mounting screws heads. A breakable flat tab in the center of the 
base can be cut and inserted in the base outer edge then pen 
marking or a label can then be used to identify the device.

Before installing this device please thoroughly read this manual and 
refer to the applicable codes for guidance on location, spacing and 
acceptable use.  Also seek guidance from the compatible control 
panel instructions for the device operation modes and the 
configuration requirements.

Note: If the detector is used with the remote indicator, then the 
voltage value of the detector must be at least 18V as the indicators 
do not operate below 18V.

SPECIFICATIONS

Dimensions:

6” Diameter, 5/8” Height

Wiring range on all terminals:

22 to 12 AWG

FIGURE 1   BASE WIRING

INSTALLATION

This base may be installed over a 4" square (MIX-4001 only), 4" 
octagonal, 3.5" octagonal, or single gang box.  The mounting may be 
performed on either the ceiling or the wall.  SLC line and remote 
output connections for the MIX-4001/4002 base are show in figure 1.  
A twisted pair cable should be used for the SLC line.  If a shielded 
cabled is used, connect the shields to the proper terminal on the 
base.  Do not connect shields to earth ground.  If a ground continuity 
wire is required by the local code, it should be a separate conductor.  
Please note that shielded cables may reduce the SLC loop length 
that can be achieved due to their high capacitance.

A breakaway tab inside the base can be inserted in the outer rim of 
the base to visibly identify each detector with their address. See 
figures 1, 3, and 4.  The detector can then be placed on the base 
using the following steps:

1. Position the detector centrally on its adapter base ensuring it is 
level.

2. Rotate clockwise applying gentle pressure. The detector will drop 
into its keyed location.

3. Continue to rotate clockwise a few degrees until the detector has 
fully engaged in the adapter base.

4. When the detector is firmly engaged, check the alignment of the 
raised reference marks on the detector and on the base (figure 4).

IMPORTANT NOTE ON BASE INSTALLATION

Disconnect loop power before installing the base.

When duplicate terminals are not provided to facilitate monitoring of 
the installation wiring connections, and there is no provision to 
prevent looping an unbroken wire around or under a terminal, the 
word "CAUTION" and the following or equivalent text in letters not 
less than 2.38 mm (3/32 inch) high shall be included on the 
installation drawing: "FOR SYSTEM MONITORING - FOR 
TERMINALS "Loop out (+)"  AND "Remote Device (+)", DO NOT 
USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO 
PROVIDE MONITORING OF CONNECTIONS.

Отзывы: