2. Declaration of Conformity
The device was tested according to the applicable standards.
Conformity was proofed. The declaration of conformity is
available at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of
the device. In case of questions that cannot be answered with
these instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to
the Federal Republic of Germany. If the device is used in other
countries it applies to the equipment installer or the user to
meet the national directions.
Safety Instructions
Keep the applicable directions for industrial safety and preventi-
on of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installati-
on or maintenance of the devices.
Only qualified personnel shall do mounting and installation
work with the devices, see section “qualified personnel”.
The information of these instructions have to be read and un-
derstood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are
persons who are well versed in the use and installation of such
devices and whose professional qualification meets the require-
ments of their work.
This includes for example:
•
Qualification to connect the device according to the VDE
specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate
it by respecting the internal directions.
•
Knowledge of safety rules.
•
Knowledge about application and use of the device within the
equipment system etc.
1. Description
The Modbus module with 10 digital inputs is designed for local
switching operations. It is suitable to record potential-free swit-
ching states as for example electrical limit switches of
ventilation valves or auxiliary contacts of power contactors. The
inputs can be operated as contact and voltage inputs (A1, 24
VAC/DC, jumper J - A2) or with actuation to GND (A2, jumper
J - A1), depending on the setting of the jumper J. The inputs can
be scanned via a Modbus-Master. Setting of the slave address, bit
rate and parity is done with the two address
switches (x1 / x10) on the front. Possible settings are addresses
00 to 99 and bit rates 1200, 2400, 4800, 9600, 19200, 38400,
57600 und 115200 Bd.
The device does not participate in bus communication if the
address is 00 (reserved for broadcast commands).
8440/899288
Digital Input Module
MR-DI10
1108311319
5. Connection Diagram
4. Wiring Diagram
3. Technical Data
Modbus Interface
Protocoll
Modbus RTU
Transmission rate
1200 ... 115200 Bd
(factory setting 19200 Bd Even)
Cabling
RS485 two wire bus with voltage
equalizing cable in bus / line topology
Supply
Operating voltage range 20 ... 28 V AC/DC (SELV)
Current consumption
85 mA AC / 75 mA DC
Relative duty cycle
100 %
Input
Input voltage
30 V DC
High-signal recognition
>10 V AC/DC
Housing
Dimensions WxHxD
1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)
Weight
83 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Mounting in series
the maximum quantity of modules
without space
connected in line is limited to 15 or to
a maximum power consumption of
2 Amps (AC or DC) per connection to
the power supply.
For any similar block of additional
modules a separate connection to the
power supply is mandatory.
Material
Housing
Polyamide 6.6 V0
Terminal blocks
Polyamide 6.6 V0
Cover plate
Polycarbonate
Type of protection
(IEC 60529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Supply and bus
4 pole terminal block
max. AWG 16 (1,5 mm²) solid wireg
max. AWG 18 (1,0 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max. 1.4 mm
(terminal block and jumper plug are
included to each packing unit)
Module connection
Input/Output
max. AWG 12 (4.0 mm²) solid wire
max. AWG 14 (2.5 mm²) stranded wire
Wire diameter
min. 0.3 mm up to max 2.7 mm
Temperature range
Operation
-5 °C ... +55 °C
Storage
-20 °C ... +70 °C
Protective circuitry
polarity reversal protection of
operating voltage
polarity reversal protection of supply
and bus
Display
Operating and bus activity green LED
Error indication
red LED
Status of the inputs
yellow LED
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Additional documentation see www.metz-connect.com