9.
Reset to factory settings
Warning of dangerous electrical voltage
Danger !
Before working on live electrical lines, the following must be observed
disconnect them from the power supply. The safety measures described in
chapter
must be observed.
Resetting the IP configuration to factory settings
1.
Power off the unit or disconnect it from the power supply.
2.
Remove the transparent upper part of the housing including the flap.
3.
Place the jumper on the middle pins 2 and 3 of the pin strip on the electronic unit.
4.
Power on the device, the status LED flashes slowly (at about 2 Hz).
5.
Remove the jumper from the pins on the pin header and plug it back into the
individual other pins. The status LED turns green.
6.
Wait until the status LED turns red, then the IP configuration is reset to factory settings.
7.
Remount the transparent upper part of the housing.
The IP configuration is then reset (see chapter
).