![Metz Connect EWIO 2 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/metz-connect/ewio-2/ewio-2_user-manual_1781387020.webp)
EWIO
2
User Manual
V 1.1 | Stand 10/2020
Seite 20 von 96
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Tel. +49 7702 533-0 | Fax +49 7702 533-433
For additional documentations look at www.metz-connect.com
Wiring Example:
5.3.3.
Digital inputs
The terminals oft the respective digital inputs are called 1+..1- to 8+..8-.
The inputs 1 to 4 are internally supplied with 15 volts. The respective minus terminals are
electrically connected to the terminals oV and GND. Inputs 5 to 8 are electrically isolated from
the device and require external voltage.
5.3.4.
Digital outputs
The terminals of the respective digital outputs are called D1 to D4. The outputs are internally
supplied with 24 volts. They are individually switchable and can be loaded up to 20 mA.
Wiring example:
5.3.5.
Analog outputs
The terminals of the respective analog outputs are called O1 to O3.
The outputs are adjustable from 0-10 Volt DC. They are individually loadable up to 5 mA.