Page 95
8.7.5 Connection notes [X2B]
Output of the analog incremental
encoder interface at the motor
D-SUB connector
at X2B
Shield connector
SK 14
Cable shield
(optional)
Connector housing
2
3
4
5
9
10
11
1
12
6
7
8
13
14
15
1
9
8
15
COS_Z0
#COS_Z0
#SIN_Z1
#SIN_Z0
SIN_Z1
#COS_Z1
COS_Z1
#R
SIN_Z0
R
GND
US
U_SENS-
TEMP+
TEMP-
Male
Figure 19:
Pin assignment: Analogue incremental encoder [X2B]
In case of wrong activated voltage supply, the encoder can be destroyed! Make sure the
correct supply voltage is activated, before connected to [X2B]!
Therefore, start the parameterisation software Metronix ServoCommander
®
and select
Parameters/Device parameters/Angle encoder settings
.
Figure 20:
Metronix ServoCommander
®
: Angle encoder settings [X2B]
Product Manual „Servo drives ARS 2100 SE“
Version 5.0