5 Electrical installation
Configuration on the device [X9]
Phoenix Contact SACC-CI-M12MSK-4PE-L180 THR T (M12, 5-pin K-coded)
Mating connector [X9]
3m Power cable, schielded: SAC-5P- 3,0-PUR/M12FSK PE SH - 1414789
Single plug: SACC-M12FSK-4PECT-CL SH
Self-assembly connectors
The connectors for self-assembly have a larger outer radius than pre-assembled
connectors. For space reasons, a self-assembly connector can therefore only be used
for [X9] or [X3]. The other plug must be pre-assembled.
Pin assignment [X9]
Figure 9: Connector "Power supply [X9]", pin side view
Pin
Name
Specification
1
L
Phase conductor/mains phase
2
N
Neutral conductor
3
ZK+
Pos. DC bus voltage
4
ZK-
Neg. DC bus voltage
PE
PE
Connection of the protective earth (ground) conductor of the
mains power supply
Cable type and configuration [X9]
We recommend using the pre-assembled cables from Phoenix Contact listed above. If
other cables are used, the minimum cross-sections listed in the following table must be
observed in any case. The power supply cable must be shielded up to the mains filter. A
single-phase circuit breaker with the listed characteristics ("Circuit breaker") must be used
in the mains supply line.
Specification (L, N, PE)
Circuit Breaker
5 x 1,0 mm², shielded (AWG 18)
K 16
Dangerous electrical voltage!
When using pre-assembled cables, always connect all available wires. For example,
life-threatening DC link voltage is present on the wires at connection 3/4.
Mounting Instructions BL 4000-M and BL 4000-D
Page 31 of 95
Содержание 9200-4104-2000
Страница 89: ...9 Appendix BL 4800 M BL 4800 D Mounting Instructions BL 4000 M and BL 4000 D Page 89 of 95 ...
Страница 91: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 91 of 95 ...
Страница 93: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 93 of 95 ...
Страница 94: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 94 of 95 ...
Страница 95: ...9 Appendix Mounting Instructions BL 4000 M and BL 4000 D Page 95 of 95 ...