Metrix SA6200A (Two-Wire) Accelerometer Replacing 3-Wire Accelerometer on BN 3500 Rack

Installation Manual

Section   

 

 

 

 

 

 

 

 

Page

1.0  PURPOSE 

                                                                               2

2.0  REFERENCES 

                                                                     2

3.0  PROCEDURE 

                                                                               2

Содержание SA6200A

Страница 1: ...c 1928171 REV A April 2022 Page 1 of 10 Metrix SA6200A Two Wire Accelerometer Replacing 3 Wire Accelerometer on BN 3500 Rack Installation Manual Section Page 1 0 PURPOSE 2 2 0 REFERENCES 2 3 0 PROCEDURE 2 ...

Страница 2: ...to installation one needs to have access to the BN software with password and username This may require a purchase in order to make changes to the set up and configuration You will need an USB to RS232 communica tions cable The USB plugs into the operator s laptop and the 9 way D type connector into the BN 3500 rack 2 0 REFERENCES SA6200A Datasheet 1009516 SA6200A Manual M9313 BN 3500 42M Datashee...

Страница 3: ...Doc 1928171 REV A April 2022 Page 3 of 10 From 3500 configuration software click File Connect Direct 5 Verify Rack Address and center Connect Password ...

Страница 4: ...Doc 1928171 REV A April 2022 Page 4 of 10 Place arrow over 3500 42M module right click on Monitors 42 42M Proximitor Seismic Monitor 3500 42M Make sure both chanels are set up as Active ...

Страница 5: ...f 10 Click drop down box for Channel Pair Type and select Acceleration Channels come in pairs 1 2 and 3 4 which mean if Channel 1 is set up as acceleration then Channel 2 must have acceleration inputs as well Click on options for Channel 1 ...

Страница 6: ...Doc 1928171 REV A April 2022 Page 6 of 10 Click on drop down box for Transducer Selection and Select Nonstandard Select Scale Factor 100 mV g ...

Страница 7: ...Doc 1928171 REV A April 2022 Page 7 of 10 Make selection for Full scale Range e g select 0 10g s pk 0 1 in s pk etc ...

Страница 8: ...ng then set up Channel 2 to required configuration Note Both Channel 1 and Channel 2 must be Acceleration From the Options screens Slot Input Output Module Type use the drop down box and select Prox Seismic I O Module Internal Termination This procedure asssumes you are connecting the accelerometer directly to the rack if not use External Termination ...

Страница 9: ...Page 9 of 10 From the Transducer Selection box Type Nonstandard select Customize This will present the Nonstandard Transducer Jumper Selection box From the Nonstandard Transducer Jumper Selection box select Prox Accel then click OK ...

Страница 10: ...022 Page 10 of 10 Make sure jumpers are applied to the Prox Seismic I O module for the Prox Accel jumpers for the associated 42M you are configuring Use only PWR B and SIG A for the wired connection for the 2 wire accelerometer ...