5534/5535/5544/5545 SIGNAL CONDITIONER SENSORS

Installation Manual

OVERVIEW

These Accelerometer Signal Conditioners ac

-

cept signals from machine casing mounted 

Metrix Seismic Accelerometer or most 

competitve accelerometers and produce a 

4-20 mA current source output proportional 

to the measured variable. The detection 

circuit is responsive to true RMS vibration 

but the output may be scaled either to peak 

or RMS units. A green LED indicates sensor 

and cable integrity. In the event of sensor 

failure, the LED extinguishes and the output 

current is driven below 3.6 mA, thereby 

signaling a malfunction. A BNC connector 

gives access to the buffered input signal for 

local analysis. Optional features for either 

model include filters and galvanic isolation 

between input, output and power supply.

INSTALLATION

Each signal conditioner is supplied with 

either a flat mounting base or a DIN rail 

adapter. When mounting in the  Metrix 

Part #7595 explosionproof housing, the 

DIN rail adapter version must be used. The 

Metrix Part #7876 and Metrix Part #8172 

weatherproof housings may be specified 

for flat base or DIN rail mounted signal 

conditioners.  For the best results, the signal 

conditioner should be installed within 1000 

feet (300 m) of the transducer.

WIRING

SENSOR (Signal Input):

 Connect the trans

-

ducer or charge amp output cable leads 

to these terminals.  If the transducer is a 

self-generating velocity pickup, polarity is 

arbitrary unless the signal polarity at the SIG 

Doc# 

 M8687 • REV E

 July 2017