Electrical Installation Safety Trainer
AD 1 - MI 3399
87
Figure 2-30: ISFL simulated errors on an IT system
In both cases the measured fault currents increased above the allowed value which
means that the contact voltage is above the safety limit during the single fault condition.
As expected in such case the tests failed.
2.5.2.2 Exercise No. 2.5-2: Verification of insulation monitor devices
(IMD)
Measuring procedure
1
To measure the single fault leakage currents select first the
IMD
function in the
Other
section.
E
xer
ci
ses
S
w
itch
Function
Site of error
ON
OFF
S15 R LOW / IMD
IT F3/1
PE outlet
> 20
Ω
< 1
Ω
S16 ISFL / IMD
IT F3/2
ISFL
approx. 6 mA (@ 230 V)
approx. 3 mA (@ 115 V)
< 1.3 mA
S17 R LOW
IT PE ref.
approx. 3.3 Ω
< 1 Ω
S18 R LOW
TN/TT F1/4
PE light
> 20
Ω
< 1 Ω
S19 R LOW / Z LOOP
TN/TT F1/2
PE outlet (3-ph.)
approx. 3.4 Ω
< 1 Ω
S20 R LOW / Z LOOP
TN/TT F2/2
PE outlet
> 2.3
Ω
< 2 Ω
S21 R LOW
MPE / PE Gas
approx. 2.2 Ω
< 1 Ω
S22 R LOW
MPE / PE Heat inst.
approx. 3.3 Ω
< 1 Ω
P
E
C
o
n
n
e
c
tio
n
S27 R
ISO
IT F3/1
L1/L2 outlet
approx. 0.45 MΩ
> 200 M
Ω
S28 ISFL/IMD
IT F3/1
L1/PE outlet
approx. 3 mA
< 1 mA
S29 I
Δ
TN/TT F2/2
L1/PE outlet
approx. 5.1 mA (@230 V)
approx. 2.5 mA (@115 V)
< 3.5 mA
S30 R
ISO
TN/TT F1/2
L1/PE outlet (3-ph.)
capacitive 1.45 MΩ
> 200 M
Ω
S31 R
ISO
/ VARISTOR
TN/TT SPD
GAS / PE
shorted
U
SPD
approx. 150 V
S32 R
ISO
TN/TT F1/2
L2/N outlet (3-ph.)
approx. 0.45 MΩ
> 200 M
Ω
S33 R
ISO
TN/TT F1/2
L1/L2 outlet (3-ph.)
approx. 0.45 MΩ
> 200 M
Ω
In
s
u
la
tio
n
r
e
s
is
ta
n
c
e
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...