Measurement on a class II appliance:
Figure 4-9: Example of the insulation test on a Class II appliance
High DC voltage test signal is applied between connected live pins and accessible
conductive parts separated from protective circuit. Each accessible conductive part shall
be tested separately.
Notes:
On/Off switches must be closed. If after the switches were closed all safety relevant
parts are not included the results will be impaired. This is often the case in
electronic or relay driven On/Off circuits. In this case leakage current tests can be
performed as an alternative.
This test cannot be applied on Class II appliances without accessible conductive
parts.
The sub-leakage test is recommended to be performed after the insulation test too.
Test voltage level is usually selected in the same level as maximum possible
supply voltage.
IT equipment not designed according to EN 60950 can be damaged by the 500 V
test voltage.
4.4.4 Sub-leakage test
Scope of test
Overall impedance between live conductors and all accessible conductive parts (earthed
and isolated) is checked with this test. Capacitive leakage paths (input filter capacitors,
transformers, cables…) are included in the result, too.
In this test the live and neutral conductors of the appliance are shorted together and
voltage of 30 - 50 V AC is applied between this point and either the earth conductor (class
I) or the probe connected to any exposed conductive part (class I and class II). The test
measures how much current passes from the live conductors into the test point.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...