Power and Voltage Quality Trainer
AD 2
– MI 3399
174
Figure 4-48: Measurement submenu
Figure 4-49: Real time measurements of powers
In this case, we have pure sinus symmetrical inductive load, without any harmonics.
Therefore the instrument shows in TOT screen, that total consumed power is
concentrated at the fundamental frequency, as non-fundamental (harmonic) power
components are almost negligible. However 15º phase shift between voltage and
current introduce 178 kVar of reactive power which in practice, can be compensated
by adding a capacitor bank.
Figure 4-50
: 15º phase shift between voltage and current
Real time measurements can be also presented in PowerView by using the Real-time
Scope button in toolbar, as shown below.
Содержание MI 3399
Страница 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Страница 28: ...Electrical Installation Safety Trainer AD 1 MI 3399 28 AD 1 MI 3399 EIS Electrical Installation Safety Trainer...
Страница 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Страница 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Страница 122: ...Power and Voltage Quality Trainer AD 2 MI 3399 122 AD 2 MI 3399 PQA Power and Voltage Quality Trainer...
Страница 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Страница 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Страница 205: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 205 AD 3 MI 3399 PAT Appliances Machines Safety Trainer...
Страница 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Страница 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...