Power Network Application Trainer
– Insulation Analysis
212
Exercise 2: Diagnostic Test
Figure 119-3: Diagnostic test measurement setup
Diagnostic test is a long duration test for evaluating the quality of the insulation
material under test. The results of this test enable the decision to be made on the
preventive replacement of the insulation material.
Method used
Simulated condition
Expected result
Un=5 kV; T = 1 min; AVG=0
Riso = 9,14 GΩ; DAR=1,36; PI=3,66;
DD=5,44
Table 73-3: Diagnostic test measuring setup/result presentation
Measuring procedure
1. Connection set up is the same as it is performed under Exercise 1.
2. Under
MAIM MENU
MEASUREMENTS
menu select
Diagnostic Test
measurement function