Power Network Application Trainer
– Power generator, transformer, coils
190
Expected result for measurements of windings combination:
A &B
A &C
B & C
Since the resistance of two windings connected in serial were measured, it is
necessary to calculate the windings resistance (formulas under point 1).
Measured
combination
Measured value
Windings
resistance
Calculated value
A
– B (R1)
794
R
HA calc
397
A
– C (R2)
800
R
HB calc
397
B
– C (R3)
800
R
HC calc
403
Table 63-3: Winding resistance result presentation
4. Connect test probes to secondary side of transformer, step 1
– winding X
A
,
between winding cennection and common point. Measured result will direct
correspond to windings resistance. Setup the parameters, as it is described under
point 3 (take care, that optimal test current and Resistance range is achieved).
Conclusion:
From the presented example we can conclude, that MI 3250 MicroOhm 10A meter is
more intended for measurement of smaller resistance. Usage of dedicated MI 3280
DTA is faster, gives as final result (using MI 3250 request final result recalculation).
Operator just needs to take care for inserting correct transformer vector group and
connection. All other tasks are done by the instrument itself.
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...