![METREL MI 3298 Скачать руководство пользователя страница 187](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927187.webp)
Power Network Application Trainer
– Power generator, transformer, coils
187
Comparing results with exercise 1 we can conclude, that:
c.
winding resistance in phase C
exceeds the measuring range of the
instrument. We can conclude, that there are definitely broken windings C.
6.3 Transformer Winding resistance measurement exercises with
MI 3250 MicroOhm 10A instrument
Figure 103-3: Winding resistance measurement setup with MI 3250
Method used
Simulated condition
Expected result
Winding resistance
measurement for current
transformer
R
HA calc.
= 397
Ω, RXA
calc.
= 4.50
Ω
R
HA calc.
= 397
Ω, RXA
calc.
= 4.46
Ω
R
HA calc.
= 403
Ω, RXA
calc.
= 4.51
Ω
Table 62-3: Winding resistance measuring setup/result presentation
Measuring procedure
1. With MI 3250 it is possible to measure the resistance of one winding at a time.
Based on the transformer vector group it is necessary to define the connecten
diagram and calculation formula for individual winding resistance, if the common
winding point (N, n) is not avaialble. Tested transforme has Yyn0 vector group.
Connection diagram for measurement of primary side od transformer winding
resistance:
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...