Power Network Application Trainer
– Earth / Ground network impedance analysing
154
Figure 90-2: Selection of test point for GPR measurements
Setup test parameters
. Select the test frequency to 55Hz, since the
DSP filtering on MI 3295M is setup to 55 Hz.
3. Press START key
on the instrument or icon
on the LCD to generate the
current through the test object.
Measuring procedure
– MI 3295M:
4. Select POTENTIAL function by using
buttons and setup measurement
parameters:
- Iset
– generated current from the MI 3290 instrument
0,151A in our test
case