Power Network Application Trainer
– Earth / Ground network impedance analysing
145
Where:
- Um
– measured voltage between test probes
- U
– calculated “real” touch voltage
U=Um* I
flt
/I
set
)
Measured Contact voltage is below the specified limits, so there is PASS indication.
4.2.4 Contact (Touch) voltage measurement with Step/Contact
instrument MI 3295S and MI 3295M
Instrument used for current generation: MI 3295S
Instrument used forcontact voltage measurement: MI 3295M
Figure 86-2: Contact (Touch) voltage setup with MI 3295S
Note:
MI3295S could generate maximal current of 55 A, so it is intended for
measurement bigger objects (comparing to MI 3290).
MI3295M is used in this application as Volt-
meter with internal resistance of 1 kΩ
(simulation of human body resistance).