MI 2142 AlphaPAT Maintenance
48
11 Maintenance
11.1 Periodic calibration
It is essential that all measurement instruments are regularly calibrated. We recommend
an annual calibration.
11.2 Fuses
There are three fuses under fuse cover:
F1 = F2 = T16A / 250V: intended for protection of test socket.
Check the fuses F1 and F2 if malfunction of mains output voltage on test socket is
noticed.
F3 = T1.6A / 250V, 20 x 5mm: instrument protection.
Check the fuse when the instrument does not respond after connection to mains supply.
Position of fuses
To change the fuse:
Disconnect all test leads and the instrument mains cord before removing fuse
cover!
Unscrew screws on fuse cover (position 6 of bottom part) and remove cover.
Replace blown fuse with the same type.
Close fuse compartment and fix the fuse cover.
Check the instrument.