EM737 CT

METERS

UK

LTD

User Manual

Smart Energy Meter

KEY FEATURES

Three phase metering

  

Standard DIN rail Format (DIN43880)

•  EN50470-3 Class B.
•  Import & Export active energy 
•  Import & Export reactive energy
•  Instant Volt, Amp, Power factor, Frequency, Active power, 
   Reactive power, Apparent power
•  Isolate pulse output and IR (DIN43864)
•  LCD display, 6 integer 2 decimal
•  Large display LCD
•  Internal transformer
•  27 CT rate can be selected
•  Optional single-phase model
•  RS232 M-Bus
•  Program by button on the front panel
•  Memory back-up (EEprom)
•  7 DIN modules
•  MID approval
•  The meter is intended to be installed in a Mechanical Environment ‘M1’, with Shock and Vibrations of low significance, as per 
   2004/22/EC Directive and should be installed in Electromagnetic Environment ‘E2’, as per 2004/22/EC Directive.

s a l e s @ m e t e r s . c o . u k    0 1 5 2 4  5 5 5  9 2 9

INDEX

1.   Safety notice

2.   Package Contents

3.   EC Type Examination Certificate - upon request

4.   Declaration of Conformity - upon request

5.   Technical description

           5.1 Performance criteria

           5.2 Meter specification

           5.3 Dimensions and sealing points

6.   Wiring diagrams

7.   Meter reading

8.   Main function

           8.1 Measuring Function

           8.2 Display function

           8.3 Electricity parameters measurement and monitoring

           8.4 Communication Function

           8.5 Alarm function

           8.6 Pulse output function

9   Programming

           9.1 Password verify

           9.2 ID setting

           9.3 Baud rate setting

           9.4 CT rate setting

           

9.5 Password setting

10.  Technical support

METERS

UK

LTD

 1. SAFETY NOTICE

The smart energy meter does not require special mechanical or electrical tools 

for its installation.   Mounting position (with any angle of tilt) has no effect on the 

measurement functions of the meter.

Connection of the meter must follow the wiring diagram. 

Incorrect connection of the meter to the electricity network will cause a major 

display problem and can also cause serious damage to the meter. 

Before connecting the meter, ensure the local conditions of the energy supply 

is consistent with the information under the model number of the meter. 

Preferably use shielded cables. Make sure that all connection cables are 

not damaged during the installation of the meter and not energized or showing 

any non-mechanical stress.

Repairs to the meter are to be made by a qualified electrician only. 

PLEASE NOTE:  The capacitors in the meter may still be charged after the meter 

is disconnected for all power.

2. PACKAGE CONTENTS

Three phase, electronic energy meter 

Instructions for assembly; ID setting; Baud rate setting; 

CT rate setting; Password setting

Содержание EM737 CT

Страница 1: ...ion 8 3 Electricity parameters measurement and monitoring 8 4 Communication Function 8 5 Alarm function 8 6 Pulse output function 9 Programming 9 1 Password verify 9 2 ID setting 9 3 Baud rate setting...

Страница 2: ...mm 75 95 25 C 55 C 3K6 25 C 55 C 1K4 75 yearly average 95 on 30 days year EN50470 3 IEC62053 21 Class B IP51 0 16mm 0 2 5mm Voltage 3 x 230 400v Operational voltage 70 Un Current A Lref 1 5A Ltr 0 15A...

Страница 3: ...12 V as the minimum bus voltage at any device must not be lower than 24 V 36 V 24 V 12 V The cable resistance therefore limits the maximum possible cable length from the MBus Master Repeater to the d...

Страница 4: ...LINE 3 LINE 3 LINE 2 LINE 1 PULSED OUTPUT KWH PULSED OUTPUT KVA PULSED OUTPUT KVA MBUS CONTACT PULSED OUTPUT KWH NEUTRAL NEUTRAL IN CT s Black S2 Red S1 Live Voltage IN 5AMP Fused 8 11 Active Test Pu...

Страница 5: ...active Power kVA Apparent Power Total Unpermitted Programming Communication Symbols LCD Alarm Indicator 8 3 ELECTRICITY PARAMETERS MEASUREMENT AND MONITORING Measure record and display voltage current...

Страница 6: ...rd 0000 are the 4 digits of the Password Set the password by pressing the Down button to decrease the digit value or Up to increase the value Press the SET button five times to move onto the next sett...

Страница 7: ...tup The interface will enter CT setup Note The default baud rate will be set at 9600BPS bd 9600 Far Distance 9 4 CURRENT TRANSFORMER RATE SETTING Press Down and Up buttons to scroll and select one of...

Страница 8: ...PLEASE NOTE It is important to take a note of the new password as one cannot bypass the system If the password is not crucial leave the password as the default 0000 10 TECHNICAL SUPPORT Any questions...

Отзывы: