Programming—IFC-1010/2020 Programming
95
The example below illustrates three ways to accomplish the simple
programming task of programming a notification appliance (control
module) on SLC loop 1 to indicate activation of an initiating device
(smoke detector) also on SLC Loop 1.
progop1
Program the smoke
detector with the
Control-By-Event:
Software
Zone Z1
Type: FZON
Solution B
No Control-By-Event
required for the smoke
detector.
Program the control
module with the
Control-By-Event:
Program the control
module with the
Control-By-Event:
OR(L1D1)
OR(Z1)
Solution C
Program the smoke
detector with the
Control-By-Event:
(Z1)
No Control-By-Event
required for the
control module.
Figure 81: Three Ways to Program a Notification Appliance
Programming
Examples
Options