Programming—IFC-1010/2020 Programming
9
Initial Programming Outline
For initial programming of the IFC-1010/2020, or for major changes and
additions, the following basic procedure is recommended to prevent errors
resulting in reprogramming and wasted time.
1.
Make copies of the Program Worksheets in the
Programming
Worksheets Technical Bulletin (LIT-448070)
.
2.
Use these worksheets to record the exact information for every
detector, module, annunciator point, and software zone in the system.
Pay special attention to the Software Type IDs listed in the
Software
Type IDs
section of this document. For voice systems, pay close
attention to AMG annunciator point commands as described in the
IFC-1010/2020 Installing the Fire Fighters Command Center
Technical Bulletin (LIT-448165).
3.
If a CRT is to be used, configure it as described in the
Installing the
IFC-1010/2020 Technical Bulletin (LIT-448155)
.
4.
Assemble and apply power to the control panel as described in the
Installing the
IFC-1010/2020 Technical Bulletin (LIT-448155).
All
system boards (including all Loop Interface Boards [LIBs]) must be
physically installed.
5.
Change the Level One and Level Two passwords as necessary. The
IFC-1010/2020 is delivered from the factory with passwords of
00000. Write down or memorize your passwords. To change the
passwords, enter the following:
Prog
)
0
)
0
)
0
)
0
!
1
)
0
@
2
^
6
Initpo1
Or
Figure 3: Key Sequence to Change Passwords
If the control panel is to be programmed before installation of LIB
Signaling Line Circuit (SLC) addressable devices, the panel exits
programming and sounds the piezo when each programmed device is not
detected. To avoid the piezo from sounding, use the following key
sequence (after entering the password):