Programming—IFC-1010/2020 Programming
65
????
Level 1 Password
alter1.cdr
!
1
Figure 56: Key Sequence to Access Option 1 (Disable Point)
Option 1 from the Alter Status menu allows the programmer to disable and
subsequently re-enable individual devices or zones. When a point is
disabled, it is no longer polled by the IFC-1010/2020.
The following example illustrates disabling Monitor Module 4 on SLC 1.
PRESS 1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK : 1
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT. CHANGE (BCKSPC TO ABORT) : L1M4
DO YOU WANT THIS POINT DISABLED? (Y=YES,N=NO) : Y
Note: The programmer or operator should never disable an SLC point
that is in alarm. The programmer should never turn on (using
Option 2 of the Alter Status menu) or program a disabled point.
Telephone (TELE) and remote page (PAGE) Type IDs cannot be
disabled.
????
Level 1 Password
alter2.cdr
@
2
Figure 57: Key Sequence to Access Option 2 (Control Module)
Option 2 from the Alter Status menu allows the programmer to selectively
turn on or off control modules from the control panel.
The following example illustrates turning on Control Module 22 on
SLC 1.
PRESS 1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK : 2
ENTER LXXMYY FOR CONTROL MODULE CHANGE (BCKSPC TO ABORT) : L1M22
DO YOU WANT POINT TO BE ON OR OFF? (Y=ON,N=OFF) : Y
Disable Point
1=DIS
Control Module
2=CTL