Programming—IFC-1010/2020 Programming
Prog
#
3
$
4
????
Level 2 Password
sec134a
Figure 38: Key Sequence to Enable or Disable Functions
Option 4 of the Partial Point Programming menu allows the programmer
to individually enable or disable, per device, the functions of Signal
Silence and Walk Test (for control modules), Alarm Verification and
Sensitivity (for addressable detectors), and Tracking (addressable detectors
and monitor modules). These functions must still be enabled or disabled,
as appropriate, for the entire system (see
Partial System Programming
in
this document). For an explanation of the functions of Signal Silence,
Alarm Verification, Sensitivity, and Tracking, see the
Glossary Technical
Bulletin (LIT-448700)
in the
IFC-1010/2020 Technical Manual.
The
Optional Features flowchart is located in Figure 39.
Note: The IFC-1010/2020 will not permit Signal Silence programming
for control modules with Software Type IDs, TELE, PWRC,
APND, TPND, and GPND. For an explanation of all Software
Type IDs, refer to the
Software Type IDs
section in this document.
Optional
Features
4=OPTNS