Preliminary—This information may change.
Miscellaneous—Emergency Stations (AFAWS-Series)
5
System Wiring
Telephone system wiring, from the FFT-7/FFT-7S through the control
point such as the XPM-8 to the warden’s station, must not be connected to
or run in the same conduit or cable tray as Signal Alarm Circuits (SLCs),
speaker circuits, strobe circuits, cable TV, or other noise producing
circuits.