CH pump standstill time from the 
thermostat 

When  the  temperature  of  the  heated  rooms  is  reached  (the  contact  of 
the room thermostat is open), the CH pump is stopped for the CH pump 
standstill  time  from  the  thermostat,  after  which  the 

CH  pump  operation 

time  from  the  thermostat 

is  activated.

 

Note:  The  following  conditions 

must be met in order to stop the pump via the room thermostat: 

 

Boiler room thermostat selection 

≠ deactivated

 

Pump shut-off from thermostat 

= YES

 

CH pump standstill time from the 

thermostat 

Min. HUW temperature 

It requires a HUW sensor to be plugged in. This parameter can be used 
for  limitation  of  possibility  to  choose  too  low  value  of  HUW  set 
temperature. 

Max. HUW temperature 

It  requires  a  HUW  sensor  to  be  plugged  in.  This  parameter  decides  on 
which  maximum  temperature  will  the  HUW  tank  be  heated  during 
dropping  down  excessive  heat  in  alarm  states.  It  is  a  crucial  parameter 
because  setting  this  for  too  high  value  can  lead  to  the  risk  of  users 
scalding  with  utility  water.  On  the  other  hand,  too  low  value  of  this 
parameter  can  lead  to a situation,  when  during  boiler  overheating  there 
will  be  no  possibility  to  drop  down  excessive  heat  into  the  HUW  tank. 
When projecting the HUW installation, there should be an assumption of 
controller malfunction. This situation can lead to dangerous level of HUW 

temperature,  leading  to  user  scalding.  It  is  advised  to  use  additional 
security precautions in form of thermostatic values.  

Boiler temperature increase from 
HUW and Mixer 

This parameter determines the increase of the set boiler temperature in 
order  to  load  the  HUW  tank,  buffer,  and  the  mixer  circuit.  The 
temperature is only increased when there is a need to do so. When the 
set temperature of the boiler is on a satisfactory level, the regulator will 
not change it in order to load the HUW tank, buffer, or mixer circuit. The 
increase of the set boiler temperature for the period of loading the HUW 
tank is signalled with the letter “C” in the main window of the display. 

HUW operation extension 

Available  after  connecting  a  HUW  sensor.  When  the  HUW  tank  is  fully 
loaded and the HUW pump is switched off, the boiler may be in danger 
of  overheating.  This  occurs  when  the  set  HUW  temperature  is  higher 
than  the  set  boiler  temperature.  The  problem  is  particularly  prominent 
when  the  HUW  pump  works  in  “SUMMER”  mode  and  the  CH  pump  is 
deactivated.  In order  to cool  the  boiler  down,  the  HUW pump  operation 
can be extended by the 

HUW operation time time 

value. 

Circulation pump standstill time 

It  is  the  time  between  periods  of  circulation  pump  operation  and  it  is 
defined  by  the  parameter 

circulation  standstill  time 

(recommended 

setting  is  between  15-40  min.)  The  circulation  pump  is  operating  in 
cycles for the time of 

circulation operation time

 (recommended setting is 

between 60 and 120s.) 

Circulation pump pperation time 

Exchanger 

It  comes  only  for  hydraulic  installations  with  heat  exchanger  between 
open and closed circuit. Available options are: 
YES (the boiler pump is operating constantly in short circuit boiler 

– heat 

exchanger,  it  is  not  excluded  e.g.  from  “SUMMER”  function  or  HUW 
priority) 
NO (standard operation of boiler pump) 

 

15.4

 

BUFFER 

 

Buffer settings 

Activation 

This parameter is used to turn on operation with the buffer. It is 
available after connecting an additional B module and buffer 
temperature sensors. 

Loading start temperature 

The  parameter 

Loading  Start  temperature

  defines  the  upper  buffer 

temperature  below  which  the  process  of  buffer  loading  is  being 
started.  This  process  will  then  be  finish  when  the  bottom  buffer 
temperature will reach defined temperature in the parameter 

Loading 

Loading stop temperature 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: