Metal-Fach ecoMAX860P2-T Скачать руководство пользователя страница 29

29 

 

13.8

 

Connection of temperature sensors 

Sensor wires may be extended using wires of 
cross-section  area  not  less  than  0.5 mm

2

Total  length  of  wires  of  each  sensor  should 
not exceed 15 m.  
Insert  boiler  temperature  sensor  into 
thermometer  well  fastened  to  boiler  shell. 
Fasten  feeder  temperature  sensor  to  the 
surface  of  feeder  screw  tube.  Insert 
temperature  sensor  of  HUW  container  into 
thermometer  well  welded  to  the  container. 
The  best  way  to  mount  mixer  temperature 
sensor is to insert it into  a sleeve located in 
the  stream  of  flowing  water,  however,  it  is 
also allowed to fasten the sensor in a contact 
manner  provided  that  the  sensor  and  the 
pipe are properly heat-insulated. 

 

Sensors shall be protected against 
loosening  from  surfaces  they  are 
mounted to. 

Make  sure  thermal  contact  between  the 
sensors and the surface which temperature is 
measured  is  good.  Apply  thermal  paste  to 
improve the contact. Pouring sensors with oil 
or water is not allowed. Sensor wires should 
be  separated  from  power  supply  wires. 
Otherwise,  temperature  indications  may  be 
erroneous.  Min.  distance  between  these 
wires should be 10 cm.  
Do  not  allow  sensor  wires  to  contact  hot 
parts of the boiler and heating system. Wires 
of temperature sensors are heat resistant to 
the temperature not exceeding 100°C.  

13.9

 

Connecting weather sensor 

The regulator cooperates only with a weather 
sensor of the CT6-P type. The sensor should 
be  installed  on  the  coldest  wall  of  the 
building,  usually  this  is  the  northern  wall, 
under  a  roof.  The  sensor  should  not  be 
exposed  to  direct  sunlight  and  rain.  The 
sensor  should  be  fitted  at  least  2 m  above 
the ground, far from windows, chimneys and 
other  heat  sources  which  could  disturb  the 
temperature measurement (at least 1,5 m). 
Connect  the  sensor  using  cable  of  0,5  mm

2

 

cross-section,  up  to  25  m  long.  Polarity  of 
the  leads  is  insignificant.  Connect  the  other 
end of the cable to the regulator. 

Attach the sensor to the wall using tackbolts. 
To  access  the  tackbolts  holes,  unscrew  the 
sensor lid. 

 

 

13.10

 

Checking temperature sensors 

The  temperature  sensor  can  be  checked  by 
measuring  its  resistance  in  a  given 
temperature. Replace the sensor if there are 
significant differences between the measured 
resistance  and  the  values  provided  in  the 
table below.  

CT4  

Ambient temp. 

°C 

Min. 

Ω 

Rated 

Ω 

Max. 

Ω 

802 

815 

828 

10 

874 

886 

898 

20 

950 

961 

972 

25 

990 

1000 

1010 

30 

1029 

1040 

1051 

40 

1108 

1122 

1136 

50 

1192 

1209 

1225 

60 

1278 

1299 

1319 

70 

1369 

1392 

1416 

80 

1462 

1490 

1518 

90 

1559 

1591 

1623 

100 

1659

 

1696

 

1733

 

 

exhaust CT2S-2, CT6-P

 

Temp. 

°C 

Min. 

Ω 

Rated 

Ω 

Max. 

Ω 

999.7 

1000.0 

1000.3 

25 

1096.9 

1097.3 

1097.7 

50 

1193.4 

1194.0 

1194.6 

100 

1384.2 

1385.0 

1385.8 

125 

1478.5 

1479.4 

1480.3 

150 

1572.0 

1573.1 

1574.2 

 
 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: