Metal-Fach ecoMAX860P2-T Скачать руководство пользователя страница 12

12 

 

information about lack thereof is displayed in 
the main window. The parameter: 

Menu 

 HUW settings 

 HUW pump 

mode

 allows the user to: 

 

disable

 

filling

 

of

 

the

 

tank,

 

parameter

 off,

 

 

set  HUW  priority,  using  the 

priority

 

parameter - in this case, the CH pump is 
deactivated  to  speed  up  filling  of  the 
HUW tank. 

 

set simultaneous operation of the CH and 
HUW pump, using parameter 

no priority

,

 

 
The  regulator  has  a  function  of  automatic, 
periodic  heating  of  HUW  container  to  70 °C 
to  eliminate  bacterial  flora  from  the  HUW 
container.  

 

Keep  the  tenants  informed  of 
activating  the  disinfection  function 
as  there  is  risk  of  being  burnt  with 
hot usable water. 

 
The  regulator  increases  the  HUW  container 
temperature  once  a  week,  at  2:00  a.m. 
Monday. After 10 minutes of maintaining the 
temperature  at  70  °C,  the  HUW  pump  is 
switched off and the boiler returns to normal 
operation.  Do  not  activate  the  disinfection 
function when the HUW support is off. 

8.11

 

 Setting HUW preset  temperature 

Preset  HUW  temperature  is  defined  by 
parameter:  

HUW settings 

 HUW preset temp. 

HUW tank hysteresis 
When the temperature drops below the HUW 
set  temperature  –  HUW  tank  hysteresis,  the 
HUW  pump  will  start  in  order  to  supply  the 
HUW tank. 

 

In  low  hysteresis  values,  the  HUW 
pump  will  start  faster  when  the 
HUW temperature drops. 

8.12

 

 HUW Circulation 

The settings are located in: 

HUW  Settings

Circulation  pump  night 

time decrease 

and 

Service Settings

→ 

CH and HUW settings 

The time settings of the circulation pump are 
analogous  to  the  settings  of  night  time 
decrease. The pump will be off in the defined 
time  periods.  At  other  times,  the  pump  will 
be  on  at 

Circulation  pump  working  time 

between  every 

Circulation  pump  stand-by 

time

.  

8.13

 

Enabling the Summer function 

To enable the SUMMER function, heating the 
WUH tank without the need of supplying the 
CH  installation,  set  the 

Summer  mode

 

parameter to on. 

Menu 

 Summer mode 

 

In  Summer  mode,  all  heat 
receivers  may  be  shut  off,  so 
before  enabling  it  please  make 
sure  that  the  boler  does  not 
overheat.  

If the weather sensor is connected, switching 
between  SUMMER  and  WINTER  mode  may 
occur automatically.   

8.14

 

 Mixer circuits settings 

Settings  for  the  first  mixer  circuit  can  be 
found in the menu:  

Menu 

 Mixer 1 settings 

Settings for other mixers can be accessed in 
next  menu  items  and  they  are  identical  for 
each circuit. 
 

Settings  for  mixer

  (without  weather 

sensor) 
It  is  necessary  to  manually  set  the  required 
water  temperature  in  the  heating  mixer 
circuit  using  parameter 

Preset  mixer  temp.

e.g.  at  a  value  of  50°C.  The  value  should 
allow 

to 

obtain 

the 

required 

room 

temperature. 
 
After  connecting  room  thermostat,  it  is 
necessary  to  set  a  value  of  decrease  in 
preset  mixer  temperature  by  thermostat 
(parameters 

Mixer room therm.) 

e.g. at 5°C. 

This  value  should  be  selected  by  trial  and 
error.  The  room  thermostat  can  be  a 
traditional thermostat (no/nc), or room panel 
ecoSTER  TOUCH.  Upon  activation  of  the 
thermostat, 

the 

preset 

mixer 

circuit 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: