“FUTURA-S”

SERIES

ACTIVE OPTO-ELECTRONIC
PROTECTIVE DEVICE “AOPD”
IN COMPLIANCE WITH THE
M A C H I N E R Y

D I R E C T I V E

2006/42/EEC

2006/42

PREFACE

This manual provides the user and/or installer with the information required for correct use
of the "FUTURA" device in the application for which it was designed, and in safety and risk-
prevention.
The manual must be kept carefully in such a way as to be immediately available should it be
required.
Contact the manufacturer for clarification, explanations or additional copies or updates of
the manual itself.

The manufacturer reserves the right to vary products and the manual without being
obliged to update previous products and manuals.

MISU_UK 2.0 - Revision 2.0 of 14-April-2010

Содержание FUTURA 114

Страница 1: ...TIVE 2006 42 EEC 2006 42 PREFACE This manual provides the user and or installer with the information required for correct use of the FUTURA device in the application for which it was designed and in s...

Страница 2: ...ica it 1 Preface 2 Contents 3 Warranty Supplied material 4 Legend 5 Precautions 6 Installation FUTURA3 FUTURA4 7 Light indicators and setting controls TX 7 1 Light indicators and setting controls RX 8...

Страница 3: ...an unsuitable working environment or phenomena not dependent on normal operation e g an unsuitable mains voltage and or frequency values d repairs carried out by persons or technical assistance centr...

Страница 4: ...detection capability DC protected area detection capability eg 14 38 76 etc working distance of the two sections Transmitter TX and Receiver RX height distance Test piece to control detection capabili...

Страница 5: ...or the device to be used Given the particular function of the device itself removal of the heads of the aluminium housings of the transmitter TX and receiver RX is prohibited No attempt should be made...

Страница 6: ...il all three LEDs on the buttons light off At this point without intervening in the protected zone and in the total absence of obsta cles repeatedly press the button only for just the number of times...

Страница 7: ...having disconnected fromthepowersupply button decreasestheworkingdistance Ifhelddownwhilethe buttonispressed reducestheworkingdistancetotheminimum allowedfor thatspecificmodel DEC INC Setting control...

Страница 8: ...han 0 7A OSSD1 or OSSD2 short circuited to GND FUTURA4 model only FAST SIMULTANEOUS BLINKING B C DEVICE STATUS OSSD1 or OSSD2 connected to the 24Vcc or OSSD1 short circuited with OSSD2 FUTURA4 model o...

Страница 9: ...g function TX FUTURA Power consumption Progressive Num Month February Year 2002 Protected height Via Como 33 A LISSONE MI ITALY Serial number Numero di serie Detection capab Capacit di rilev Model Mod...

Страница 10: ...the device is a constant establishing the speed at which the operator approaches the danger point established at 2 m per second is the time in milliseconds deriving from the sum of the time t1 taken b...

Страница 11: ...EDIUM RANGE RED HIGH RANGE GREEN ALERT RED ALARM YELLOW BLOCK BLK RED MUTING F4 ORANGE MANUAL RESTART 2 VOLTAGE FREE SWITCHES 0 7A 40Vdc ac E D M XTERNAL EVICE ONITOR START RESTART INTERLOCK MUTING F4...

Страница 12: ...LLOW LOW RANGE YELLOW MEDIUM RANGE RED HIGH RANGE GREEN ALERT RED ALARM YELLOW BLOCK BLK RED MUTING F4 ORANGE MANUAL RESTART 2 VOLTAGE FREE SWITCHES 0 7A 40Vdc ac E D M XTERNAL EVICE ONITOR START REST...

Страница 13: ...t Female socket Male plug If the function TEST is not used short circuit the conductors 4 5 and connect them to the 0V of power supply blue 3 If the functions E D M and START RESTART are not used shor...

Страница 14: ...D M and START RESTART are not used short circuit the conductors 3 4 and connect them to the 0V of power supply red shield 8 P N the E D M function works only if loads K1 K2 Kn are with forced interlo...

Страница 15: ...8 2 7 8 5 1 5 0 5 1 5 1 5 44 6 5 3 5 3 5 41 6 5 15 5 3 5 5 TOP HEAD SECTION VIEW 3 20 24 1 5 6 2 7 8 5 1 5 0 5 1 5 1 5 44 41 13 5 3 Fig 15 Fig 16 Fig 17 Fig 18 7 13 4MA 15 46 41 15 HOUSING CROSS SECTI...

Страница 16: ...reen indicator is lit with the machine stationary and power to the on in the presence of an obsta cle in the protected area the red indicator is lit moving parts are not accessible to personnel Any ex...

Страница 17: ...calibration Below are a number of examples of order codes with relative comments for different models of the FUTURA optoelectronic light curtains model designed to protect from risks up to category 3...

Отзывы: