background image

Merlin CO2 Monitor   

 

 

 

 

 

                          User Guide 

 

 

Rev: 1  05-19

 

7  

Circuit Board 

 

 

 

 

 

1. 

POWER – Line Voltage Input 110-120VAC, L N 

2. 

Alarm relay, volt free connection to Merlin system. 

3. 

Pre alarm relay, volt free connection to Merlin system. 

4. 

Temperature relay. 

5. 

0-10V output, low voltage connection. 

6. 

Audible alarm switch, ON = ON / 1 = OFF 

 
 

High and low voltage wires should not be run in the same conduit 

 

 
 

Maintenance 

 

To keep your device in good working order, you must follow these steps: 
 

 

DO carefully remove any accumulated dust from the outer enclosure once a month. 
 

 

NEVER use detergents or solvents to clean your device – this may permenantly or temporarily 
damage the gas sensing elements. 
 

 

NEVER spray air fresheners, hair spray, paint or other aerosols near the device. 

 

 

NEVER paint the device. Paint will seal vents and interfere with the device. 

 
 
 
 

Содержание CO2 Monitor 1500 ppm

Страница 1: ...Merlin CO2 Monitor User Guide Rev 1 05 19 1 Gas Safety Products Merlin CO2 Monitor 1500 2800 4500 ppm User Guide Please read this guide carefully and retain for future use...

Страница 2: ...nstallation Operation 4 2 1 Mounting the CO2 Monitor 4 2 2 Mains Supply 4 2 3 Alarm Relay 4 2 4 Pre Alarm Relay 4 2 5 Temperature Relay 4 2 6 0 10 Volt DC Output 5 2 7 Audible Alarm 5 3 LED Indication...

Страница 3: ...nsor element is 10 Years Do not apply lighter gas or other aerosols to the detector this will cause extreme damage Never ignore your device when in alarm This device requires a continual supply of ele...

Страница 4: ...e above 2800ppm and automatically switch back once the levels have dropped below 2750ppm Model CO2 Monitor 4500ppm This will switch over should the level of Co2 rise above 4500ppm and automatically sw...

Страница 5: ...500 1750 7 2V per 1000ppm 1750 2000 8 2000 2400 9 2400 2800 10 2 7 Audible Alarm There is a switch on the circuit board to activate de activate the audible alarm ON audible alarm on default 1 audible...

Страница 6: ...ppm 4 Specification Power Supply 110 120VAC 50Hz Max 2VA Gas Sensor Carbon Dioxide Non Dispersive Infrared Detector NDIR ABC Logic Self Calibration CO2 Measuring Range 0 9999ppm Resolution 1ppm Accura...

Страница 7: ...High and low voltage wires should not be run in the same conduit 6 Maintenance To keep your device in good working order you must follow these steps DO carefully remove any accumulated dust from the o...

Страница 8: ...ove warranty period In no event shall the manufacturer be liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the co...

Отзывы: