background image

mcr WIP PRO

 multi-blade fire damper                              

MERCOR” S.A. – 

All rights reserved to modifications without prior notice

 

25/25 

 

Any  damage or failure of the equipment caused by  improper operation, tampering, failure to conduct 
periodic  technical  inspection  and/or  maintenance  established  in  the  Operating  and  Maintenance 
Manual, section “SERVICING AND MAINTENANCE”. 

 

Any damage beyond reasonable control of “MERCOR” SA, and specifically: caused by force majeure, 
such  as  torrential  rainfall,  flooding,  hurricanes,  inundation,  lightning  strike,  power  grid  overvoltage, 
explosion, hail, collision with aircraft, fire, avalanche, landslide and indirect damage due to those causes. 
Torrential rainfall is understood as any rainfall with the effectiveness factor of 4 or higher in accordance 
with the definition of the Polish Institute of Meteorology and Water Management - National Research 
Institute (IMGW-PIB). If the effectiveness factor value  specified  in the preceding  sentence cannot be 
reasonably  established, the actual condition and  extent of damage shall  be considered at the site  of 
their origin as the action of torrential rain. Hurricane is understood as any wind with a minimum speed 
of 17.5 m/s (and damage shall be recognised as caused by hurricanes if the effects of such weather 
phenomenon has been found in the direct vicinity of the damaged property). 

 

Damage due to failure to immediately report any defect found. 

 

Deterioration in the quality of coatings due to natural weathering/ageing. 

 

Defects caused by abrasive or aggressive cleaning agents. 

 

Damage caused by aggressive external influence, specifically chemical or biological in nature, or when 
the  origin  of  which  is  related  to  the  production  processing  or  activity  carried  out  within  the  facility 
protected by the equipment or in its direct vicinity. 

 

Wearing parts and consumables (e.g. gaskets/seals), unless they have defects of workmanship and/or 
material. 

 

Damage caused by improper transport, handling, unloading and/or storage of the equipment. 

 

Damage caused by installation of the equipment in violation of this Operating and Maintenance Manual 
and/or good construction practice. 

 

The equipment and/or parts thereof with removed or damaged nameplate (rating plate) and/or warranty 
seals. 

11.  The  buyer/warranty  rights  holder  is  required  to  operate  the  equipment  properly  and  carry  out  technical 

inspection  and  maintenance  in  accordance  with  the  section  “MAINTENANCE  AND  SERVICING”  in  the 
following Operating and Maintenance Manual.  

12.  This warranty shall be made immediately void and null if: 

 

The  buyer/warranty  rights  holder  modifies  the  product  design  without  prior  authorisation  from 
“MERCOR” SA. 

 

Periodic technical inspection and/or maintenance is not carried out per schedule and/or is carried out 
by unauthorised personnel or service providers not authorised to do so by “MERCOR” SA and/or the 
equipment has not been properly operated. 

 

Unauthorised personnel attempts any intervention in the product outside of the normal operation and 
maintenance of this equipment. 

13.  Any circumstances listed in Item 10 will relieve “MERCOR” SA from the obligation of surety.  

 
 
The relevant provisions of the Polish Civil Code shall apply to all matters not regulated in these Warranty Terms & 
Conditions. 
 

 

Содержание mcr WIP PRO

Страница 1: ... MERCOR S A ul Grzegorza z Sanoka 2 80 408 Gdańsk PL tel 48 58 341 42 45 tel fax 0 58 341 39 85 TECHNICAL MANUAL Fire damper type mcr WIP PRO Version WIP PRO 19 11 27 11 FIRE VENTILATION SYSTEMS ...

Страница 2: ... INTENDED USE 3 4 DESIGN OPERATING PRINCIPLE 4 5 DEVICE IDENTIFICATION 7 6 INSTALLATION 7 6 1 PRE ASSEMBLY INSPECTION 7 6 2 INSTALLATION OPENING 7 6 3 EMBEDDING 8 6 4 ELECTRICAL CONNECTIONS 15 7 TRANSPORT STORAGE CONDITIONS 18 8 MAINTENANCE SERVICING 18 9 WARRANTY TERMS CONDITIONS 19 Technical Manual designations Option available Option unavailable ...

Страница 3: ...stems mcr WIP PRO V shut off fire dampers for mixed fire ventilation systems mcr WIP PRO V M transfer fire dampers mcr WIP PRO T relief fire dampers mcr WIP PRO T G The dampers cannot be operated in systems exposed to dust except for when they are included in a special individually developed program of service and technical inspections Fire resistance ______________________________________________...

Страница 4: ...ly by tripping an electric axial actuator with a return spring caused by isolation from the voltage supply automatically by tripping the thermal trigger and the driving spring shut off fire dampers for fire ventilation systems mcr WIP PRO V In the normal operating position the dampers are closed Opening of the dampers to the safety position follows remotely by tripping an electric axial actuator w...

Страница 5: ... V V M T G BLE 230 S V V M M T G BFL 230 T S V V M T G BLE 24 S V V M M T G BFL 24 T ST S V V M T G EXBF 230 S V V M M T G BFN 230 T S V V M T G EXBF 24 S V V M M T G BFN 24 T ST S V V M T G BF 230 TN S V V M M T G BF 24 TN ST S V V M T G BF24 TN TL S V V M M T G Spring gear RST S V M T G RST KW1 S S V M T G RST KW1 24P S V M T G RST KW1 24I S V M T G RST KW1 230P S V M T G RST KW1 230I S V M T G ...

Страница 6: ... possibility of disassembly the control release mechanism in order to perform maintenance or technical review The mcr WIP PRO dampers can be installed in the following building partitions i e walls or ceilings masonry concrete walls min 120 mm thick in variants S T V V M masonry walls made of bricks or blocks min 120 mm thick in variants S T V V M panel walls min 125 mm thick in variants S T V V M...

Страница 7: ...ar type Even number of blades Odd number of blades Belimo BF BLF BFL BFN BE BLE Z mm H 2 123 30 Z mm H 2 61 5 30 RST KW1 S RST KW1 24P Z mm 0 Z mm 0 6 3 EMBEDDING SETTING THE DAMPER ___________________________________________ The mcr WIP PRO fire damper will work properly if the damper blade rotation axis is horizontal The control release gear may be placed on the right or on the left side of the ...

Страница 8: ...stops To do this the fire damper must be covered with plastic film or other suitable material and remain so until the embedding and finishing is done In order to ensure the fire resistance of the fire separation element the damper blades rotation axis cannot be situated outside the wall face If the fire partition wall thickness is similar to the length of fire damper it is recommended to install t...

Страница 9: ... Plasterboard rim 100x12 5 mm 3 Solid wall min thickness 120 mm 4 Mortar 5 Thermal trigger installed in the duct 100 mm from the fire damper Fig mcr WIP PRO fire damper installation example in solid walls made of bricks or stone blocks with a minimum fire resistance rating of EI120 Installation gap 10 mm 1 2 3 4 5 10 min 120 ...

Страница 10: ...rd thickness 12 5 mm 3 Mineral wool 4 Mortar 5 Structural profile 6 Thermal trigger installed in the duct 100 mm from the fire damper 7 Plasterboard rim 100x12 5 mm Fig Installation example of the mcr WIP PRO fire damper in a drywall structure with a minimum fire resistance rating of EI120 Installation gap 10 mm 1 2 3 4 5 6 7 10 min 125 ...

Страница 11: ...r 1 Plasterboard thickness 12 5 mm 3 Mineral wool 4 Mortar 5 Structural profile 6 Masking grid 7 Plasterboard rim 100x12 5 mm 8 duct Fig Installation example of the mcr WIP PRO fire damper in a drywall structure with a minimum fire resistance rating of EI120 with masking grid and duct Installation gap 10 mm 7 6 1 2 3 4 5 8 ...

Страница 12: ...damper 1 Plasterboard thickness 12 5 mm 3 Mineral wool 4 Mortar 5 Structural profile 6 Masking grid 7 Plasterboard rim 100x12 5 mm Fig Installation example of the mcr WIP PRO fire damper in a drywall structure with a minimum fire resistance rating of EI120 with masking grid Installation gap 10 mm 1 2 3 4 5 7 6 min 125 ...

Страница 13: ...IP PRO The masking grid can be supplied as a modular by the damper manufacturer The solution of system masking grates dedicated in particular to usable spaces with high architectural and functional requirements allows covering additional damper with any other masking grid while meeting the requirements of mcr WIP PRO fire flap classification ...

Страница 14: ...prior notice 14 25 1 Fire damper 2 Concrete floor slab min thickness 150 mm 3 Mounting Z bars 4 Cement mortar 5 Thermal trigger installed in the duct 100 mm from the fire damper 6 Steel duct 7 Plasterboard rims 100 mm x 12 5 mm 1 2 3 4 5 6 7 10mm min 150 1 2 3 4 5 Z1 Z1 Z1 Z1 Z2 Z2 Z3 Z3 A B ...

Страница 15: ...50 mm min fire resistance rating EI120 Installation gap 10 mm The Z bars are installed from below of the fire damper Z bars are selected accordingly to the fire damper frame width CAUTION The Z bars are not delivered in package with fire damper set If the installation opening is prepared with a place for control release mechanism B use Z3 Z bars with dimensions as shown in the figure below If the ...

Страница 16: ...damper MERCOR S A All rights reserved to modifications without prior notice 16 25 Fig Mounting Z bars installation of the mcr WIP PRO fire damper in a concrete ceiling slab with min thickness 150 mm min fire resistance rating R120 ...

Страница 17: ...r WIP PRO fire damper BxH 4 A building element with fire resistance equal or higher to the building envelope resistance For example a brick wall 5 e g mortar Installation of the mcr WIP PRO fire damper as a multiple damper set a set of 4 Other configurations of the mcr WIP PRO dampers modules can be made consisting of two or more dampers while maintaining the minimum distances between the dampers ...

Страница 18: ... the rivet nuts in the corners of the damper In case of need for additional anchorage of the ventilation duct to the damper it is possible to use hexagon type self tapping screws K type ST 3 5x13mm made of galvanized steel according to DIN 7504 The assembly is possible to the steel frame of the damper in distances shown below Rys Installation of ventilation ducts ...

Страница 19: ...ning 7 W 8 5 W for spring holding 2 W 3 W Sizing apparent power 10 VA 11 VA Appliance class III II Ingress protection rating IP 54 IP 54 Auxiliary circuit breaker 2xSPDT 6 3 A 250V 2xSPDT 3 A 250V activation position degrees 5 80 5 80 Torque motor 18 Nm 18 Nm spring 12 Nm 12 Nm Cable connection motor L 0 9 m 2x0 75 mm2 2x0 75 mm2 auxiliary circuit breaker 6x0 75 mm2 6x0 75 mm2 Movement time 0 90 m...

Страница 20: ...55 C 30 55 C 30 55 C Sound pressure level motor max 58 dB A max 58 dB A max 58 dB A max 58 dB A Technical data actuators BFL24 BFL24 T BFL230 BFL230 T BFN24 BFN24 T BFN230 BFN230 T Power supply AC 24 V 50 60 Hz DC 24 V AC 220 240 V 50 60 Hz AC 24 V 50 60 Hz DC 24 V AC 220 240V 50 60 Hz Power demand when putting the spring under tension when in standby 2 5 W 0 7 W 3 5 W 1 1 W 4 W 1 4 W 5 W 2 1 W Ap...

Страница 21: ...erved to modifications without prior notice 21 25 Connection diagram for the BF24 Tand BF230 T actuators Connection diagram for the BFL24 T BFL230 T BFN24 T BFN230 T BF24 TN and BF230 TN actuators Connection diagram for the BE24 BLE24 BE230 and BLE230 actuators ...

Страница 22: ...ltage housed tolerance of 24V 10 or 230V 10 Power supply devices other than listed above may cause malfunction and will not be covered by the warranty conditions EXBF actuators Technical specifications EXBF 24 EXBF 230 Zone 1 2 21 22 ATEX classification II 2 GD EEx d IIC T6 Power supply 24 V AC 20 50 60 Hz 24 VDC 10 20 230 V AC 14 50 60 Hz Power demand for spring tensioning 7 W 8 W for spring hold...

Страница 23: ...r consumption X 3 5 W 1 6 W 4 5 W 2 5 W Holding force X 12 daN 12 daN 12 daN 12 daN Thermal trigger trip point 72 C 2 C WK1d WK2d limit switch NO NC switching contact 5A 230V AC Switch trigger 3 87 tolerance 2 Limit switch operating temperature 25 85 C Electrical connection X release cable 0 6 m 2x0 5 mm2 limit switch cable 0 6 m 6x0 5 mm2 Rotation angle 92 Movement time Max 2s spring Sense of rot...

Страница 24: ...al access to the equipment by removing thermal insulation suspended ceiling and other installations as required and applicable to warrant unobstructed access Inspection ports e g type mcr KRW are recommended for the equipment installed in ducts In the case of roof mounted equipment provide access to the area via ladders or elevated platforms Refer all matters related to technical inspection mainte...

Страница 25: ...cleaning agents Damage caused by aggressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing parts and consumables e g gaskets seals unless they have defects of workmanship and or material Damage caused by impro...

Отзывы:

Похожие инструкции для mcr WIP PRO