mcr WIP PRO
multi-blade fire damper
„
MERCOR” S.A. –
All rights reserved to modifications without prior notice
23/25
Connection diagram for the EXBF actuators
Caution:
For proper operation of a device equipped with electrical actuators, it is recommended that the rated voltage housed
tolerance of 24V±10% or 230V±10%. Power supply devices other than listed above may cause malfunction and will
not be covered by the warranty conditions.
RST/KW1 trigger control gear
The RST/KW1/S version has the limit switches installed in the gear itself. The electrical connections shall be made
by connecting the properly labelled conductors to the electrical system. A fusible trigger is installed in the gear. The
dampers with the RST/KW1/230I, RST/KW1/230P mechanisms, are supplied with the RST/KW1/24... triggering and
control mechanism, together with the 230/24V transformer module type MP230/24.
RST/KW1/S
RST/KW1/24I
RST/KW1/24P
RST/KW1/24I
+MP230/24
RST/KW1/24I
+MP230/24
Supply voltage
X
24 V – 48 V DC
24 V – 48 V DC
230V AC
230V AC
Power consumption
X
3.5 W
1.6 W
4.5 W
2.5 W
Holding force
X
12 daN
12 daN
12 daN
12 daN
Thermal trigger trip point
72°C +-2°C
WK1d / WK2d limit switch
NO/NC (switching contact)
5A, 230V AC
Switch trigger
3°, 87° – tolerance: +/- 2°
Limit switch operating
temperature
-25 ...+85°C
Electrical connection
X
- release: cable 0.6 m, 2x0.5 mm
2
- limit switch: cable 0.6 m, 6x0.5 mm
2
Rotation angle
92°
Movement time
Max. 2s - spring
Sense of rotation
CCW
Gear weight
1.2 kg
1.4 kg
1.4 kg
1.5 kg
1.5 kg
KW1 gear power supply:
WK1 limit switch
WK2 limit switch
Wire number: 1-2
Wire number: 3-4 – NO (normally open)
Wire number: 6-7 – NO (normally open)
Wire number: 4-5 – NC (normally closed)
Wire number: 7-8 – NC (normally closed)
Connection diagram for transformer module type MP230/24
Caution! - The location of the limit switches is showed for the fire damper in the safety position.
The RST/KW1 trigger control can work with the MP230/24 module. If the MP230/24 module is installed, the fire
damper can be powered/controlled with voltage 230 V AC.
The proper performance of the device with electric actuators requires the rated supply voltage of 24 V ±2% or 230 V
±2%, as applicable. Other voltage values may cause operating malfunctions, that are not covered by the product
warranty.