background image

Output Module - Extension Module Type mcr R04xx. Operation and Maintenance Manual.

 

 

Strona 5 z 19 

 

If the 230 V~ mains power supply to the module or the control unit is missing, the smoke 

vents can only be opened in the event of an alarm; the ventilation function is blocked to protect 
the batteries from discharging. 

Caution: do not leave the unit without mains power for more than 72 h with the batteries 

connected, due to the possibility of damage to the batteries. In case of using the module to 
power  mcr  PROSMOKE  FS  CE  curtains,  this  time  is  up  to  6.5  h  (see  operation  and 
maintenance manual for mcr PROSMOKE FS CE curtains). 

4. Transport, delivery, storage 

The modules are delivered assembled in individual packages. Batteries are supplied 

separately. The devices should be stored in dry rooms, in temperatures 0

C÷40

C. 

5. Module mounting 

The module should be mounted near the devices it controls, in a location that allows 

access to the device. During mounting, disconnect all power sources to the equipment being 
installed. 

Use  conductor  types  compliant  with  the  local  regulations,  with  appropriate  cross 

sections. 

Install the module in the following order: 

1. 

Fix the enclosure to the wall with steel fasteners matched to the substrate 
m

aterial:  fasteners  with  a  minimum  diameter  of  Ø8,  e.g.  M8,  are 

recommended 

(note

: do not drill holes in walls through the enclosure).  

2. 

Make  electrical  connections  according to  the  attached  diagrams  (connect 
control units, actuators, line termination resistors). 

3. 

Connect the unit to the mains supply. Attach the connectors to the battery 
terminals. Turn on the overcurrent circuit breaker inside the enclosure. The 
230 V~ LED should light up. The ACTIVE and FAULT LEDs should remain 
unlit;  when  connected  to  the  mcr  9705  control  unit  with  door  automation 
function, the ACTIVE LED will be lit. 

4. 

Verify system operation by sounding the alarm from all available sources. 

5. 

The device is ready to operate after the batteries are charged (up to 48 h 
after the first mains connection, if the connected actuators are not used). 

6. Operation 

 

The module is basically a maintenance-free device; however, to ensure the efficiency 

of the smoke ventilation system the condition of the device should be checked according to 
the following list: 

1.  Check the status of the module's control units  - whether they signal any damage 

(daily). 

2.  Check the power supply to the extension modules (every 3 days or so). If the power 

supply decay has lasted (or is suspected to have lasted) for more than 72 hours, 
an  authorised  "MERCOR"  S.A.  service  centre  should  be  called  to  check  the 
batteries' condition. In case of using the module to power mcr PROSMOKE FS CE 
curtains, this time is up to 6.5 h (see operation and maintenance manual for mcr 
PROSMOKE FS CE curtains) 

3.  Verify system operation by activating the alarm signal, then clear the alarm signal. 

Check  that  connected  devices  have  opened  and  closed  correctly  (1  time  per 
month). 

 

 

Содержание mcr R0424-1

Страница 1: ... rew C Status Wydany OPERATION AND MAINTENANCE MANUAL Operating instructions Power supply equipment Output Module Extension Module type mcr R0424 1 mcr R0424 2 mcr R0448 1 mcr R0448 2 mcr R0448 4 mcr R0424 K mcr R0448 K ...

Страница 2: ...ibility Related documents Certificate of Constancy of Performance CNBOP PIB No 1438 CPR 0590 confirming compliance with the requirements of EN 12101 10 2005 AC 2007 Certificate of Admittance CNBOP PIB No 3149 2018 Declaration of Performance No 090 HO 2018 of 06 05 2018 EU Declaration of Conformity No 089 HO 2018 of 07 03 2018 The above documents can be downloaded from the website of MERCOR S A www...

Страница 3: ...n mcr PROLIGHT mcr S THERM mcr ULTRA THERM smoke exhaust vents smoke exhaust windows equipped with MCR W or MCR L actuators mcr PROSMOKE FS CE curtains mcr R0424 1 mcr R0424 2 mcr R0448 1 mcr R0448 2 mcr R0448 4 modules or to control and supply with 24V voltage electric motors of mcr PROSMOKE CE C1 smoke curtains mcr R0424 K mcr R0448 K modules The modules can also be used to power other devices o...

Страница 4: ... for the 230 V supply network rated at D 10 A Tab 1 Fuse rating summary Module type Fuse F2 F3 F4 F5 F6 0424 1 25 A 0424 2 25 A 12 A 12 A 0448 1 50 A 0448 2 25 A 25 A 0448 4 50 A 12 A 12 A 12 A 12 A 0424 K 25 A 0448 K 50 A The device is equipped with indication of the following states 1 Power supply 230 V present green LED on 2 Fault yellow LED on signal transmitted to the control unit active in c...

Страница 5: ...ure 2 Make electrical connections according to the attached diagrams connect control units actuators line termination resistors 3 Connect the unit to the mains supply Attach the connectors to the battery terminals Turn on the overcurrent circuit breaker inside the enclosure The 230 V LED should light up The ACTIVE and FAULT LEDs should remain unlit when connected to the mcr 9705 control unit with ...

Страница 6: ...ers related to technical inspections maintenance and repairs of the equipment you may consult the representatives of MERCOR S A service phone 58 341 42 45 from 8 a m to 4 p m e mail serwis mercor com pl 8 Warranty terms and conditions 1 MERCOR S A grants a 12 month quality guarantee for equipment starting from the date of purchase unless the agreement provides otherwise 2 If during the term of gua...

Страница 7: ... has occurred damages due to aggressive external factors especially chemical and biological ones 7 Each defect under guarantee should be reported to a local representative of MERCOR S A immediately i e within 7 days of its discovery 8 Applications can be made by phone at 48 58 341 42 45 by email to claim mercor com pl or by sending a letter to MERCOR S A 80 408 Gdańsk Grzegorza z Sanoka 2 9 The Bu...

Страница 8: ...ce of output line continuity check resistors 10 k Standby time without mains voltage after this time the module can start the connected devices once 72 h Number of control groups 1 Load capacity and number of output lines mcr R0424 2 mcr R0424 1 mcr R0448 4 mcr R0448 2 mcr R0448 1 mcr R0424 K mcr R0448 K 2x output lines of max 12 A 1x output line of max 24 A 4x output lines of max 12 A 2x output l...

Страница 9: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 9 z 19 10 Wiring diagrams Fig 2 Wiring diagram for mcr R0424 1 module for use with smoke vent actuators ...

Страница 10: ...r use with mcr PROSMOKE FS CE curtain unit PM installation box in close proximity to mcr PROSMOKE FS CE curtains MECU curtain control unit Note 1 additional information in Technical and Operation Documentation of mcr PROSMOKE FS CE curtains 2 max number of mcr PROSMOKE FS CE curtain modules acc to curtain s operation and maintenance manual ...

Страница 11: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 11 z 19 Fig 4 Wiring diagram for mcr R0424 2 module ...

Страница 12: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 12 z 19 Fig 5 Wiring diagram for mcr R0448 1 module ...

Страница 13: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 13 z 19 Fig 6 Wiring diagram for mcr R0448 2 module ...

Страница 14: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 14 z 19 Fig 7 Wiring diagram for mcr R0448 4 module ...

Страница 15: ...le Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 15 z 19 Fig 8 Wiring diagram for mcr R0424 K module Fig 9 Wiring diagram for mcr R0448 K module No on actuator lines No on actuator lines ...

Страница 16: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 16 z 19 11 Certificate of approval ...

Страница 17: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 17 z 19 ...

Страница 18: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 18 z 19 ...

Страница 19: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 19 z 19 ...

Отзывы: