background image

 
 

Nr dok: HO.21.01252 rew.: 

C

 

Status: Wydany

  

 

 

 

 
 

OPERATION AND MAINTENANCE MANUAL 

 

Operating instructions 

 

 

 

Power supply equipment 

 

Output Module 

– Extension Module  

type: 

mcr R0424-1 
mcr R0424-2 
mcr R0448-1 
mcr R0448-2 
mcr R0448-4 

mcr R0424-K 
mcr R0448-K

Содержание mcr R0424-1

Страница 1: ... rew C Status Wydany OPERATION AND MAINTENANCE MANUAL Operating instructions Power supply equipment Output Module Extension Module type mcr R0424 1 mcr R0424 2 mcr R0448 1 mcr R0448 2 mcr R0448 4 mcr R0424 K mcr R0448 K ...

Страница 2: ...ibility Related documents Certificate of Constancy of Performance CNBOP PIB No 1438 CPR 0590 confirming compliance with the requirements of EN 12101 10 2005 AC 2007 Certificate of Admittance CNBOP PIB No 3149 2018 Declaration of Performance No 090 HO 2018 of 06 05 2018 EU Declaration of Conformity No 089 HO 2018 of 07 03 2018 The above documents can be downloaded from the website of MERCOR S A www...

Страница 3: ...n mcr PROLIGHT mcr S THERM mcr ULTRA THERM smoke exhaust vents smoke exhaust windows equipped with MCR W or MCR L actuators mcr PROSMOKE FS CE curtains mcr R0424 1 mcr R0424 2 mcr R0448 1 mcr R0448 2 mcr R0448 4 modules or to control and supply with 24V voltage electric motors of mcr PROSMOKE CE C1 smoke curtains mcr R0424 K mcr R0448 K modules The modules can also be used to power other devices o...

Страница 4: ... for the 230 V supply network rated at D 10 A Tab 1 Fuse rating summary Module type Fuse F2 F3 F4 F5 F6 0424 1 25 A 0424 2 25 A 12 A 12 A 0448 1 50 A 0448 2 25 A 25 A 0448 4 50 A 12 A 12 A 12 A 12 A 0424 K 25 A 0448 K 50 A The device is equipped with indication of the following states 1 Power supply 230 V present green LED on 2 Fault yellow LED on signal transmitted to the control unit active in c...

Страница 5: ...ure 2 Make electrical connections according to the attached diagrams connect control units actuators line termination resistors 3 Connect the unit to the mains supply Attach the connectors to the battery terminals Turn on the overcurrent circuit breaker inside the enclosure The 230 V LED should light up The ACTIVE and FAULT LEDs should remain unlit when connected to the mcr 9705 control unit with ...

Страница 6: ...ers related to technical inspections maintenance and repairs of the equipment you may consult the representatives of MERCOR S A service phone 58 341 42 45 from 8 a m to 4 p m e mail serwis mercor com pl 8 Warranty terms and conditions 1 MERCOR S A grants a 12 month quality guarantee for equipment starting from the date of purchase unless the agreement provides otherwise 2 If during the term of gua...

Страница 7: ... has occurred damages due to aggressive external factors especially chemical and biological ones 7 Each defect under guarantee should be reported to a local representative of MERCOR S A immediately i e within 7 days of its discovery 8 Applications can be made by phone at 48 58 341 42 45 by email to claim mercor com pl or by sending a letter to MERCOR S A 80 408 Gdańsk Grzegorza z Sanoka 2 9 The Bu...

Страница 8: ...ce of output line continuity check resistors 10 k Standby time without mains voltage after this time the module can start the connected devices once 72 h Number of control groups 1 Load capacity and number of output lines mcr R0424 2 mcr R0424 1 mcr R0448 4 mcr R0448 2 mcr R0448 1 mcr R0424 K mcr R0448 K 2x output lines of max 12 A 1x output line of max 24 A 4x output lines of max 12 A 2x output l...

Страница 9: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 9 z 19 10 Wiring diagrams Fig 2 Wiring diagram for mcr R0424 1 module for use with smoke vent actuators ...

Страница 10: ...r use with mcr PROSMOKE FS CE curtain unit PM installation box in close proximity to mcr PROSMOKE FS CE curtains MECU curtain control unit Note 1 additional information in Technical and Operation Documentation of mcr PROSMOKE FS CE curtains 2 max number of mcr PROSMOKE FS CE curtain modules acc to curtain s operation and maintenance manual ...

Страница 11: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 11 z 19 Fig 4 Wiring diagram for mcr R0424 2 module ...

Страница 12: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 12 z 19 Fig 5 Wiring diagram for mcr R0448 1 module ...

Страница 13: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 13 z 19 Fig 6 Wiring diagram for mcr R0448 2 module ...

Страница 14: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 14 z 19 Fig 7 Wiring diagram for mcr R0448 4 module ...

Страница 15: ...le Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 15 z 19 Fig 8 Wiring diagram for mcr R0424 K module Fig 9 Wiring diagram for mcr R0448 K module No on actuator lines No on actuator lines ...

Страница 16: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 16 z 19 11 Certificate of approval ...

Страница 17: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 17 z 19 ...

Страница 18: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 18 z 19 ...

Страница 19: ...Output Module Extension Module Type mcr R04xx Operation and Maintenance Manual Strona 19 z 19 ...

Отзывы: