USER MANUAL 

 

Power supply units for sound alarm systems  

type  

ZDSO400-DR2, ZDSO400-DR4 

 

complying with:  

 standards:  EN-54-4:1997+A1:2002+A2:2:2006  &  EN-121001-10:2005, 

certificate of constancy of performance 1438-CPR-0319 

 

04.08-2015 

 

 

1.

 

TECHNICAL DESCRIPTION .............................................................................. 2

 

2.

 

OPERATION PRINCIPLE ................................................................................... 6

 

3.

 

INSTALLATION AND CONNECTION ............................................................... 10

 

4.

 

FIRST START ................................................................................................... 11

 

5.

 

OPERATION ..................................................................................................... 14

 

6.

 

SERVICING ....................................................................................................... 16

 

7.

 

ADDITIONAL INFORMATION .......................................................................... 17

 

 

 

Prepared by: 

 

Mr. Adam Kretek 

Checked by: 

 

Mr. Zdzisław Klimasara 

Verified by: 

 

Mr. Dariusz Cygankiewicz 

Approved by:          Mr. Grzegorz Szandar 

 
Documentation N

o

:   0546.00.95-02.2 

Содержание ZDSO400-DR2

Страница 1: ...pe ZDSO400 DR2 ZDSO400 DR4 complying with standards EN 54 4 1997 A1 2002 A2 2 2006 EN 121001 10 2005 certificate of constancy of performance 1438 CPR 0319 04 08 2015 1 TECHNICAL DESCRIPTION 2 2 OPERAT...

Страница 2: ...device damage Do not cover ventilation openings doing so may result in device damage Provide a free space of at least 8 cm at the sides of the device enabling its proper ventilation The device must b...

Страница 3: ...R2 SIE BATERIA ADOWANIE USZKODZENIE 42 5 465 31 8 483 445 328 45 A B Fig 1 View and nominal dimensions of ZDSO400 DR2 power supplies ZDSO400 DR4 SIE BATERIA ADOWANIE USZKODZENIE 483 445 465 87 44 5 32...

Страница 4: ...ouring connectors of the circuit equalizing voltages of the battery banks M 3 A socket for connecting the temperature sensor TEMP SENSOR 4 Two input sockets for external fault indication EXT FAULT 1 a...

Страница 5: ...double sockets for connecting the network controller and other VAS modules designed to work with 24V power supply ADDITIONAL OUTPUT 24V They can also be used for connecting the smoke and heat system d...

Страница 6: ...em the battery of the same capacity and type must be used When you need to replace a battery please replace their whole set You can use in the system various battery capacities in various strings e g...

Страница 7: ...Mains Battery Charging DIGITAL MEASUREMENT PANEL FAN RGR M M Fault IB Mains fault Bat fault Gen fault Ext flt 1 Ext flt 2 Aux 1 2 BAT 24V BAT 24V Temp sensor EXTERNAL SYGNALLING INPUT REMOTE ETHERNET...

Страница 8: ...0 DR4 power supply When the mains present the power supply maintains the external battery banks in their fully charged state Power supply s operation is controlled by the microprocessor controller whi...

Страница 9: ...or if the voltage difference exceeds 0 1V The use of voltage equalising circuit requires an additional connection to be introduced between the M terminal of a given battery string and the median point...

Страница 10: ...e and separately the network controllers and other VAS modules supplied with the 24V voltage The sockets located in the back panel allow for connection of single amplifiers with power of up to 500W us...

Страница 11: ...External fault indication systems should be connected using the YnTKSY 1x2x0 8 type cables the cross section of 0 8 mm 2 Output of remote indication Outputs of remote relay indication are implemented...

Страница 12: ...he sum of the initial resistance and the permissible battery circuit resistance increase is indicated in the power supply certificate 1438 CPR 0319 and it cannot be higher than 50m The resistance valu...

Страница 13: ...off and the FLT LED should be on The both relays of MAINS FLT and GENERAL FLT should come into the idle mode the terminals position should be according to the figure near the connector The state of th...

Страница 14: ...odes indicating type of measurement are switched off This position is active only then when an operation error has been detected in the system and the fault indication has been activated A list of par...

Страница 15: ...on Normal operation state when the mains present off No mains or rectifier fault BATTERY yellow on Battery operation no mains or rectifier fault off Normal operation state when the mains present CHAR...

Страница 16: ...it can be done only after disconnecting the mains and the battery bank The VAS system personnel can exchange the above mentioned breakers only If other circuit breakers used within the power supply un...

Страница 17: ...6 2 Warranty and after warranty repairs should be performed by service of the manufacturer or by an authorised service partner of the manufacturer 7 Additional information 7 1 Remarks of the manufact...

Страница 18: ...ternal temperature measurement error P36 Overcurrent of battery 1 connector E37 Overcurrent of battery 2 connector E38 Overcurrent of battery 3 connector E39 Overcurrent of battery 4 connector E40 Bat...