- 20 -
Installation manual
M-WRG-II M/MB
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
9.3.1 Cable types
Part no.
Type of ventilation
unit
Type of mains cable Type of control cable
700000
700001
700002
701000
701001
701002
M-WRG-II P
M-WRG-II P-F
M-WRG-II P-FC
M-WRG-II E
M-WRG-II E-F
M-WRG-II E-FC
NYM-J 3x1.5 mm
2
or
NYM-J 4x1.5 mm
2
(*)
No control cable
700010
700011
700012
701010
701011
701012
M-WRG-II P-T
M-WRG-II P-T-F
M-WRG-II P-T-FC
M-WRG-II E-T
M-WRG-II E-T-F
M-WRG-II E-T-FC
NYM-J 3x1.5 mm
2
or
NYM-J 4x1.5 mm
2
(*)
— InControl pushbutton
sensor:
J-Y (St) Y 10x2x0.6 mm /
J-Y (St) Y 10x2x0.8 mm
— Three-step rotary switch:
J-Y (St) Y 4x2x0.6 mm /
J-Y (St) Y 4x2x0.8 mm
— BCD encoding:
J-Y (St) Y 4x2x0.6 mm /
J-Y (St) Y 4x2x0.8 mm
700020
700021
700022
701020
701021
701022
M-WRG-II P-M
M-WRG-II P-M-F
M-WRG-II P-M-FC
M-WRG-II E-M
M-WRG-II E-M-F
M-WRG-II E-M-FC
NYM-J 3x1.5 mm
2
or
NYM-J 4x1.5 mm
2
(*)
Building management
system, Modbus, Loxone,
KNX:
J-Y (St) Y 2x2x0.6 mm /
J-Y (St) Y 2x2x0.8 mm
700030
700031
700032
701030
701031
701032
M-WRG-II P-S 485
M-WRG-II P-S 485-F
M-WRG-II P-S 485-FC
M-WRG-II E-S 485
M-WRG-II E-S 485-F
M-WRG-II E-S 485-FC
NYM-J 3x1.5 mm
2
or
NYM-J 4x1.5 mm
2
(*)
Touch Control network:
J-Y (St) Y 2x2x0.6 mm /
J-Y (St) Y 2x2x0.8 mm
Table 2: Types of mains cable and control cable for each ventilation unit type
(*)
If the external control input is used