11 Options for ventilation mode
11.1
External control input
11.1.1 Description
With the external control input supplied as standard, the M-WRG-II unit has an additional
input terminal for 230 V AC (working voltage range: 85 V AC to 265 V AC / 50-60 Hz) to
which a switch, time switch, motion detector or similar may be connected.
The external control input is equipped with a time-delay relay that can be used to set a
switch-on delay and a run-on time:
— Switch-on delay:
the M-WRG-II unit does not start until the set time has elapsed.
— Run-on time:
the M-WRG-II unit does not switch to the previously active ventilation program until
the set time has elapsed.
Windowless rooms can be ventilated in accordance with DIN 18017-3 in combination with
the M-WRG-II O/NOF option, part no. 721004.
11.1.2 Factory defaults and possible adjustment ranges
Parameter
Factory defaults
Possible adjustment ranges
Air flow
60 m
3
/h
10 to 100 m
3
/h
Switch-on delay
1 min
0 to 240 min
Run-on time
15 min
0 to 240 min
NOTICE
The above parameters can be changed either at the factory or using the optional wire-
less remote control M-WRG-FBH.
11.1.3 M-WRG-II O/EST-1, part no. 721005, and M-WRG-II O/EST-2, part no. 721006
The following options may be selected in addition to the external control input which is
supplied as standard:
— M-WRG-II O/EST-1: without switch-on delay, needs to be fitted at the factory
— M-WRG-II O/EST-2: without run-on time, needs to be fitted at the factory
11.2
M-WRG-II O/PARM, part no. 721000
This option is used to set special air output parameters for all M-WRG-II units. It needs to
be fitted at the factory.