19U QSFP SDR/DDR/QDR InfiniBand Switch Platform User’s Manual
Rev 1.7
Mellanox Technologies
27
3.2.4 Installing the Cable Holder
1. Place the Cable holder next to the rack and identify the holes for the caged nuts. The numbers on
the cable holders should face each other.
2. Put the caged nuts into the previously identified holes in the rack.
3. Screw the cable holder onto the rack using the screws provided.
4. Repeat steps 1 to 3 for the second cable holder.
3.2.5 Power Connections
The switch includes integrated hot-swap power supplies which support up to eight load-sharing
1000W supply units. The slots for the eight power supply units (PSUs) are on the front panel and
are labelled 1-8. Three are placed horizontally across the top and five are mounted vertically along
the right side of the chassis. Each PSU has a dedicated AC inlet. This design enables the optional
use of separate main and backup AC feeds. The input voltage is Autorange, 100-240 VAC, 50Hz
or 60Hz. The output voltage for the PSUs is 48V. The power cords should be standard 3-wire AC
power cords including a safety ground.
Before starting any procedure on the MTS3610 Switch system put an ESD prevention wrist strap
on your wrist and connect to the MTS3610 Chassis.
Holes for con-
necting the
cable holder
to the rack
X 8
Left side rack
Top side
X 8
Right side rack
Bottom side